Carrier CCU Manual De Regulatión página 68

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

11 - COMMISSIONING
Faults
Low temperature
High temperature
Low humidity
Humidity sensor
High humidity
Humidity sensor
68
Sources
Causes
Sensor
Temperature
Malfunction
sensor
Drift in dehumidification 
mode
Sensor
Temperature
Malfunction
sensor
Room overheated
Sensor
Malfunction
Sensor
Malfunction
Excessively high humidity
Solutions
• Check the sensor
• Replace the sensor
• Check the stability of the control
• Check the operation of the heating valve or the electric heater
• Internal load insufficient
• Check the sensor
• Replace the sensor 
• Check the stability of the control
•   C heck the operation of the cooling valve, the compressors
• Revise the room loads
• Check the sensor 
• Replace the sensor 
• Check the stability of the control
•   C heck the operation of the humidifier
• Revise the room loads
• Check the sensor
• Replace the sensor
• Check the stability of the control
•   C heck the operation of the cooling valve, the compressors
• Revise the room loads

Publicidad

Tabla de contenido
loading

Tabla de contenido