Indoor Unit
Bottom Panel
Air Intake
Preliminary Site Survey
Voltage supply fl uctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be independent
of welding transformers which can cause high supply
fl uctuation.
Ensure that the installation location is convenient for
wiring and piping.
Figure A
A
C
B
All manuals and user guides at all-guides.com

INSTALLATION DIAGRAM

Top Panel
Air Discharge Louver
Air Intake Grille
Air Intake
Air Discharge

INSTALLATION OF THE INDOOR UNIT

Standard Mounting

Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall mounting
bracket for fl oor standing), and check for its alignment with
the unit as shown in Figure A. Also, check that the hangers
are secured and the base of the fan coil unit is leveled in both
horizontal directions, taking into account the gradient for
drainage fl ow as recommended in Figure B.
All dimensions are in mm
1-5
Wrap the Insulated pipe with the
fi nishing tape from bottom to top
Thermal Insulation
Figure B