Siemens SIRIUS 3SB3 Manual De Instrucciones página 6

Ocultar thumbs Ver también para SIRIUS 3SB3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 10
Protection against physical contact:
– Solder terminal:
Connection of contact blocks and lamp holders
behind the front panel
– Screw-type terminal and spring-loaded terminal:
safe against finger touch according to VDE 0660, Part 514 and BGV A3
Degree of protection according to IEC 60 529 (VDE 0470, Part 1)
– Connection of contact blocks and lampholders behind
the front plate
– Switching spaces of contact blocks behind front plate
– 3SB3000-7AA10 acoustic indicator
– Lock with key control
– Twin pushbutton, 3SB323.-7BA10 acoustic indicator
– Pushbutton with extended stroke
– Illuminatable backing plate
– Plastic actuator and indicator
– With protective caps
– Metal actuator and indicator
Mechanical endurance
– Pushbuttons and contact blocks
– Actuators, rotary or maintained contact
– Illuminated pushbuttons
– Lock with key control
– Monitored contact block
Electrical endurance
– for AC-15 duty, with 3RT1015 to 3RT1026 contactors
– for DC-12, DC-13 duty:
For DC the endurance of the contacts is dependent not only on the breaking cur-
rent but also on the voltage, the inductance of the circuit and the operating speed.
Operating frequency
Conventional thermal current I
th
Rated operational voltage U
(V)
e
Rated operational current I
(A)
e
with 50 / 60 Hz AC
I
/ AC-12 screw / spring-loaded terminal
e
I
/ AC-12 solder connection
e
I
/ AC-15 screw / spring-loaded terminal
e
I
/ AC-15 solder connection
e
with DC
I
/ DC-12 screw / solder connection /
e
spring-loaded terminal
I
/ DC-13 screw / solder connection /
e
spring-loaded terminal
Contact stability test voltage / test current
Short-circuit protection
(without any welding according to IEC 60 947-5-1)
– DIAZED fuse links
Utilization category gL / gG
for safety applications, only
fuses complying with IEC / EN 60269-1 gL / gG
– Miniature circuit-breaker
with C characteristic acc. to IEC 60 898 (VDE 0641)
u
and
s
data
Rated voltage:
– Contact block
– BA9s lampholder
– Wedge base W2 x 4.6 d lampholder
– Lampholder with integrated LED
– Illuminatable backing plate
– Continuous current
– Switching capacity
6
IP00
IP20
IP40
IP40
IP54
IP65
IP65
IP65
IP66
IP67
IP67 /
Nema type 4
6
10 x 10
5
3 x 10
6
3 x 10
5
1 x 10
5
3 x 10
6
10 x 10
1000 op. cycles / hour
10 A
24
48
110 230 400
10
10
10
10
10
10
10
10
10
6
6
6
6
3
4
4
4
4
10
5
2.5
1
3
1.5
0.7
0.3
5 V / 1 mA
10 A TDz, 16 A Dz
10 A
10 A
300 V AC
125 V AC; 2.5 W
60 V AC; 1 W
24 V AC / DC
110 V AC
230 V AC
24 V AC/DC
10 A
A300; R300; A600
same polarity
Permissible conductor cross-sections
– Screw terminal connection:
finely stranded with end sleeves DIN 46228
solid
solid with end sleeves DIN 46228
solid or stranded
– Spring-loaded terminal connection:
solid or finely stranded without end sleeves
finely stranded with end sleeves DIN 46228
solid or stranded
– Solder connection (solder pins)
– Plug for illuminatable backing plate:
finely stranded with end sleeve DIN 46228
solid
solid or stranded
Length of conductor insulation to be stripped
– Screw terminal connection
– Spring-loaded terminal connection
– Plug for illuminatable backing plate
Tightening torque
– of the screw on the metal holder
– of the screw on the plastic holder
– of holder earthing screw
– of terminal screws
– at the plug of the illuminatable backing plate
Matching screwdriver sizes
– Slot-head screwdriver
– Slot-head screwdriver (for holder)
– Cross-head screwdriver (Pozidriv)
– Torx screwdriver
– Slot-head screwdriver (spring-loaded terminal)
Safety measure for plastic range
Safety measures are met automatically when the actuators and lens assemblies
are mounted in metal front plates and enclosures. When mounted in insulated
enclosures, the "protective insulation" safety requirements are met.
• Safety measure for metal range
Warning
Grounding is required for voltages above safety extra-
low voltage.
Mounting in front plates / enclosures made of electrically non-conductive
material (Fig. X):
Each individual actuator must be earthed; earthing screw available as acces-
sory.
Mounting in front plates made of electrically conductive material:
Because of its protruding tip, the countersunk holder screw (TORX T10) pro-
vides both anti-rotation protection and contacting with the front plate. If surfaces
are thickly painted, the contacting and the anti-rotation protection can be
improved by screwing the screw in further (approx. 0.5 revolution). The operator
must ensure the effectiveness of the protective measure by checking (on his
own responsibility).
Information about
• Lamp holder with lamp test function 3SB3400-1L:
The negative potential (L-) must not be connected to the protective conductor
if the direct voltage is larger than the safety extra-low
(DIN EN 60204-1 / VDE 0113-1).
• Metal range:
It is only permissible to illuminate the selector switch with an LED insert.
• Metal and plastic range:
For EMERGENCY-STOP devices equipped with 1 or 2 contact block(s) in
connection with support 3SB3901-0AB one of the contact blocks must be
mounted in the center position.
Note
Siemens is not responsible for damage or injury in the
event of improper usage or inappropriate dismantling
other than opening in the intended manner.
Any improper handling can cause serious physical
injury.
:
2 x 0.5 ... 1.5 mm²
2 x 1 ... 1.5 mm²
2 x 0.5 ... 0.75 mm²
2 x AWG 18 ... 14
2 x 0.25 ... 1.5 mm²
2 x 0.25 ... 0.75 mm²
2 x AWG 24 ... 16
0.8 x 0.8 mm²
1 x 0.25 ... 1.5 mm²
1 x 0.14 ... 1.5 mm²
1 x AWG 28 ... 16
8 ... 10 mm
7 ... 9 mm
7 mm
1.5 Nm
1.0 Nm
1.0 Nm
0.8 Nm
0.22 Nm
5.5 mm x 1 mm
4.5 mm x 0.8 mm
PZD 0, PZD 2
T10
3.5 mm x 0.5 mm
voltage.
Order No.: 3ZX1012-0SB30-1AA1

Publicidad

Tabla de contenido
loading

Tabla de contenido