Siemens SITRANS LR200 HART Guía Para La Puesta En Marcha Rápida página 11

Ocultar thumbs Ver también para SITRANS LR200 HART:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 74
Passive Shunt Diode Barriers
A well regulated supply voltage is required.
Note:
Manufacturer
MTL
MTL
Stahl
Stahl
Active barriers (repeating barriers)
Manufacturer
MTL
MTL
Stahl
Instructions specific to hazardous area installations
(Reference European ATEX Directive 94/9/EC,
The following instructions apply to equipment covered by certificate number SIRA
03ATEX2142X:
1.
For use and assembly, refer to the main instructions.
2.
The equipment is certified for use as Category 1G equipment.
3.
The equipment may be used with flammable gases and vapors with apparatus group IIC
and temperature class T4.
The equipment is certified for use in an ambient temperature range of –40 °C to 80 °C.
4.
5.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
7.
Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
Page EN-10
SITRANS LR200 (HART) – QUICK START MANUAL
Part Number
787SP+ (Dual channel)
7787P+ (Dual channel)
9001/01-280-100-10 (Single channel)
9002/01-280-110-10 (Dual channel)
Part Number
706
7206
9001/51-280-110-14
Annex II, 1/0/6)
(continued on next page)
7ML19985QL83

Publicidad