Maximum limitation
69
of room temperature
Effect of room tem-
70
en
perature
Boost of room tem-
71
perature setpoint
with boost heating
Parallel displace-
72
ment of heating
curve
Type of heating
73
curve adjustment
Block "3-position actuator for heating circuit"
Maximum limitation
81
of flow temperature
Minimum limitation
82
of flow temperature
Maximum rate of
83
increase of flow
temperature
Excess flow tem-
84
perature mixing
valve
Actuator running
85
time
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
Setting --.- = limitation deacti-
--.- °C
vated
(--.- / 0...35)
°C
...................
Function possible only with
room unit / room temperature
sensor
Gain factor for effect of room
4
temperature
(0...20)
.........................
Function possible only with
room unit / room temperature
sensor
5 °C
(0...20)
°C
...................
Value in °C room temperature
0.0 °C
°C
(−4.5...+4.5)
...................
0 = analog adjustment
0
1 = digital adjustment on the
(0...2)
.........................
2 = digital adjustment via bus
--- °C
Setting --- = function deacti-
(--- / 0...140)
°C
vated
...................
No safety function
--- °C
Setting --- = function deacti-
(--- / 0...140)
°C
vated
...................
--- °C/h
Setting --- = function deacti-
(--- / 1...600)
°C/h
vated (function prevents crack-
..............
ing noise in piping)
10 °C
Setpoint boost for precontroller
(0...50)
°C
in interconnected plants
...................
120 s
(30...873)
s
......................
74 319 0619 0 a
17.04.2008
controller and via bus
only
50/288