133 Actuator opening
time
134 Actuator closing
time
135 P-band (Xp) d.h.w.
en
control
136 Integral action time
(Tn) d.h.w. control
Block "Derivative action time d.h.w. heating via heat exchanger"
137 Derivative action
time (Tv) d.h.w.
control
Block "Multifunctional relay"
141 Function of multi-
functional relay
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
120 s
(10...873)
s
......................
120 s
s
(10...873)
......................
32.0 °C
(1.0...100.0)
°C
...................
120 s
(10...873)
s
......................
0 s
s
(0...255)
......................
0 = no function
0
1 = outside temperature switch
(0...7)
.........................
2 = ON / OFF according to time
3 = relay ENERGIZED in the
4 = relay ENERGIZED during
5 = relay ENERGIZED during
6 = relay ENERGIZED when
7 = manually ON / OFF accord-
If operating line 54 = 3, or oper-
ating line 125 is not 0, this op-
erating line cannot be changed
74 319 0619 0 a
17.04.2008
(set operating lines
143...145)
switch (select time switch
on operating line 146)
case of fault
occupancy time
occupancy time incl. optimi-
zations
there is a demand for heat
ing to operating line 142