Block "Switching program 3"
151 Weekday (for
switching program
3)
152 Start of first ON
en
period
153 End of first ON
period
154 Start of second ON
period
155 End of second ON
period
156 Start of third ON
period
157 End of third ON
period
Block "Service functions and general settings"
161 Outside tempera-
ture simulation
162 Relay test
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
1 = Monday
1-7
2 = Tuesday, etc.
(1...7)
.........................
1-7 = entire week
06:00
(00:00...24:00)
.........................
22:00
(00:00...24:00)
.........................
--:--
(00:00...24:00)
Switching program 3
.........................
--:-- = period inactive
--:--
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
--.- °C
Simulation automatically termi-
°C
(--.- / −50...+50)
nated after 30 minutes
...................
--.- = no simulation
0 = normal operation
0
(0...13)
1 = all contacts open
2 = burner stage 1 ON K4
3 = burner stages 1 ON K4
4 = circulating pump / bypass
5 = charging pump ON M3
6 = heating circuit mixing valve
7 = heating circuit mixing valve
74 319 0619 0 a
and 2 ON / burner modula-
tion actuator OPEN K5
pump ON M1
OPEN Y1
CLOSED Y2
17.04.2008