195 Controller's soft-
ware version
196 Identification code
of room unit
en
Block "Solar d.h.w."
201 Temperature differ-
ential ON solar
202 Temperature differ-
ential OFF solar
203 Collector frost pro-
tection
204 Collector over tem-
perature protection
205 Evaporation heat
carrier
206 D.h.w. charging
temperature maxi-
mum limitation
207 D.h.w. storage tank
temperature maxi-
mum limitation
208 Collector start func-
tion gradient
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
Display function
Display function
8 °C
Temperature differential be-
°C
(0...40)
tween collector and storage
...................
tank
4 °C
Temperature differential be-
°C
(0...40)
tween collector and storage
...................
tank
--- °C
Setting --- = No collector frost
°C
(--- / –20...5)
protection
...................
105 °C
Setting --- = No collector over
°C
(--- / 30...260)
temperature protection
...................
140 °C
Setting --- = No collector pump
°C
(--- / 60...260)
protection
...................
80 °C
°C
(8...100)
...................
90 °C
No safety function
°C
(8...100)
...................
--- min/°C
Setting --- = Function deacti-
min/°C
(--- / 1...20)
vated
...........
74 319 0619 0 a
17.04.2008
64/288