Overall earth resistance without RCD tripping (Ra
Voltage range P-PE, P-N:
Voltage range N-PE:
Frequency:
Global earth resistance in systems with Neutral (3-wire) – (30mA or higher RCD)
Range []
0.05 9.99
10.0 199.9
Global earth resistance in systems with Neutral (3-wire) – (6mA and 10mA RCD)
Range []
0.05 9.99
10.0 199.9
Global earth resistance in systems withot Neutral (2-wire) – (30mA or higher RCD)
Range []
0.05 9.99
10.0 99.9
100 1999
Global earth resistance in systems withou Neutral (2-wire) – (6mA and 10mA RCD)
Range []
0.05 9.99
10.0 99.9
100 1999
Contact voltage (measured during RCD and Ra
Range [V]
0 Ut LIM
Phase rotation with 1 test lead
Voltage range P-N, P-PE[V]
100 265
Measurement is only carried out by direct contact with metal live parts (not on insulation sheath).
Voltage drop
Range [%]
0 100
Environmental parameters (AUX)
Measurement
°C
°F
RH%
DC voltage
Lux
Values lower to ±1mVDC are zeroed; Values lower to 0.1mVAC are zeroed
100V 265V
<10V
50/60Hz 5%
Resolution []
0.01
0.1
Resolution []
0.01
0.1
Resolution []
0.01
0.1
1
Resolution []
0.01
0.1
1
Resolution [V]
0.1
Resolution [%]
0.1
Range
-20.0 60.0°C
-4.0 140.0°F
0.0% 100.0%RH
-1999.9mV -1.0mV
1.0mV 1999.9mV
0.01 20.00lux
1 2klux
1.00 20.00klux
EN - 7
EASYTEST-COMBI519-COMBI521
)
test)
Frequency range
50Hz/60Hz 5%
Resolution
0.1°C
0.1°F
0.1%RH
0.1mV
0.01Lux
1Lux
0.01kLux
Quick reference guide
Accuracy
(5rdg +8dgt)
Accuracy
(5rdg +30dgt)
Accuracy
(5rdg +8dgt)
Accuracy
(5rdg +30dgt)
Accuracy
-0%, +(5.0 rdg + 3V)
Accuracy
(10%rdg + 4dgt)
Accuracy
(2%rdg +2dgt)