Troubleshooting (continued): DALI Functions
Symptom
Cannot add a DALI device to a zone
after a "Build System" or "Address all" command
has been run
DALI device at full brightness cannot be controlled
DALI devices do not flash when running the "Build
System" command
DALI device is not affected by a level change
DALI device light levels can be lowered, but not
raised to full On
"Build System" command does not find DALI loads
®
Possible Causes
Zone is not set to DALI
D1 and D2 are not connected
DALI devices are not addressed
DALI devices are miswired
DALI device is not assigned to a zone
DALI device is being affected by the daylight sensors
D1 and/or D2 are miswired or not connected
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
Remedy
Set the zone to DALI
Check D1 and D2 connections on the back of the
GRAFIK Eye QS with DALI
Check voltage: Minimum voltage of 12 V
Address DALI devices
Check D1 and D2 wiring, and power wiring to DALI
devices
Run the "Address all" command and assign the DALI
device to a zone
Recalibrate the associated daylight sensors
Check wiring; if wiring is correct, call Lutron Technical
Support
QS with DALI Quick Installation and Operation Guide 23
®