Wiring conventional and heat pump systems
Aux
Y
G
O
L
R
2H/1C Heat Pump System TH3210D
C
24 Vac common [3]
B
Changeover valve energized in
heating [5]
R
Power [1]
L
Sends output when set to Em. Heat [8]
O
Changeover valve energized in
cooling [5]
G
Fan relay
Y
Compressor contactor
Aux Auxiliary heat relay [9]
E
Emergency heat relay [9]
W
Y
G
O
Rc
R
B
1H/1C System TH3110D
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power [1]
G
Fan relay
Y
Compressor contactor
W
Heat relay
W
Y
G
O
Rc
R
B
1H/1C System TH3110D (2 transformers)
C
24 Vac common [3, 4]
R
Power (heating transformer) [1, 2]
Rc
Power (cooling transformer) [1, 2]
G
Fan relay
Y
Compressor contactor
W
Heat relay
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
[1] Power supply. Provide disconnect means
and overload protection as required.
[2] Remove jumper for 2-transformer sys-
tems.
[3] Optional 24 Vac common connection.
[4] Common connection must come from
cooling transformer.
[5] Use either O or B terminals for change-
over valve.
B
C
C
(1 transformer)
C
W
Y
G
O
Rc
R
1H/1C Heat Pump System TH3110D [7]
C
24 Vac common [3]
B
Changeover valve energized in
heating [5]
R
[R+Rc joined by jumper]
Rc
Power [1]
O
Changeover valve energized in
cooling [5]
G
Fan relay
Y
Compressor contactor [6]
W
[W+Y joined by jumper]
W
O
Rc
R
Heat Only System TH3110D
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power [1]
W
Heat relay
W
G
O
Rc
R
Heat Only System with Fan TH3110D
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power [1]
G
Fan relay
W
Heat relay
Y
G
O
Rc
R
Cool Only System TH3110D
C
24 Vac common [3]
R
[R+Rc joined by jumper]
Rc
Power [1]
G
Fan relay
Y
Compressor contactor
[6] Use a small piece of wire (not supplied) to
connect W and Y terminals.
[7] Set fan operation switch to Heat Pump
(see page 5) and configure system type
for heat pump (see page 6).
[8] L terminal sends a continuous output
when thermostat is set to Em. Heat.
Connect to Honeywell Home zoning pan-
els to switch the panel to Emergency Heat.
[9] Install field jumper between Aux and E if
there is no emergency heat relay.