It is possible to connect the temperature sensor via:
1 - The inverter analog outputs (see Section 15 - Faults and Alarms of the Programming Manual which is supplied with
the inverter in CD).
2 - Accessory IOE-01.
3 - External protection relay with alarm output connected to a digital input of the inverter configured as general enable or
without external fault.
F
For further information on the motor installation and maintenance, refer to the instruction booklet
Note!
supplied with it.
3 - Inverter installation and connections
F
Read the CFW11 User's Manual which is supplied with the inverter before installing, powering up or
Note!
operating the inverter.
For the Sensorless PM control (P0202=7), at the speed range of 0 to 240 rpm, the IGBTs are driven with
switching frequency of 5 kHz (regardless the value set in P0297 - switching frequency). On the CFW11
F
Note!
inverters of mechanics E or above, derating must be applied on the output current so as to allow their
operation with switching frequency of 5 kHz - see Chapter 8 of the CFW11 User's Manual. Exception:
models 0142T2 and 0180T2 when dimensioned in HD (P0298=Heavy-Duty).
Install the inverter according to Chapter 3 - Installation and Connection of the User's Manual.
g
Prepare the drive and power up the inverter according to Chapter 5 - Power-up and Start-up of the User's Manual.
g
4 - Configuration of the inverter
The configuration through the "Oriented Start-up" results in the automatic modification of the content
F
Note!
of parameters and internal variables of the inverter regarding the control and the motor. That ensures a
stable operation of the control and maximum efficiency of the motor.
Start the parameterization through the "Oriented Start-up" Menu [02], and the main parameters are displayed in a
g
logical sequence on the HMI. During the Oriented Start-up routine, the "Config" (configuration) status will be indicated
on the top left corner of the HMI.
In order to perform the oriented start-up, follow the procedures described below by entering the motor nameplate
g
data.
Electric motor
3
355J/H-06
~
PERMANENT MAGNET MOTOR
INVERTER SUPPLY
1000
RPM
PF
2
F
70
T
INS CL.
IE4
97.0
IE code
IP55
ALT
1
5
4 | W22 Magnet Drive System
®
1
3
5
315
3009
kW
Nm
S1
DUTY
380
640
V
A
0.87
1.00
SF
50°C
K
AMB
96.8
96.7
( 100%)
( 75%)
( 50%)
1000
3552
m.a.s.l.
kg
3
2
and W50 Magnet
3PT9
C
US
MOD.TE2+F0X0X
IEC 60034-1
06
Poles=
W2-2
U2-2
V2-2
2.40
Lq(mH)=
W2-1
U2-1
V2-1
U1-2
V1-2
W1-2
1.50
Ld(mH)=
U1-1
V1-1
W1-1
345
L1
L2
L3
Ke=
6322-C3(60g)
MOBIL POLYREX EM
6319-C3(45g)
4000 h
4
1 - Rated voltage
2 - Rated speed
3 - SF -Service Factor
4
4 - Lq, Ld and Ke
5 - Rated current