Basic Operation

Do not connect or disconnect battery packs
when the UPS is running on battery power.
If you connect any external batteries, set
the Battery Charge Level Switches (see
to the down position. This will increase your
UPS system's charger output so that the
additional batteries charge faster.
Caution!
DO NOT set the Battery Charge Level Switches to the down position
without an external battery connected. There is a risk of damaging
the UPS system's internal battery system.
Buttons (Front Panel)
"ON/OFF/STANDBY" Button
To turn the UPS ON: with the UPS plugged into a live AC wall outlet*,
press and hold the "ON/OFF/STANDBY" button for one second.**
Release the button. If utility power is absent, you can "cold-start"
the UPS (i.e.: turn it ON and supply power for a limited time from its
batteries***) by pressing and holding the "ON/OFF/STANDBY" button for
one second.**
To turn the UPS OFF: with the UPS ON and receiving utility power, press
and hold the "ON/OFF/STANDBY" button for one second.** Then unplug
the UPS from the wall outlet. The UPS will be completely OFF.
* After you plug the UPS into a live AC outlet, the UPS (in "Standby" mode) will automatically
charge its batteries, but will not supply power to its outlets until it is turned ON. ** The alarm
will beep once briefly after the indicated interval has passed. *** If fully charged.
"MUTE/TEST" Button
To Silence (or "Mute") UPS Alarms: briefly press and release the
MUTE/TEST button.*
To Run a Self-Test: with your UPS plugged in and turned ON, press and
hold the MUTE/TEST button. Continue holding the button until the alarm
beeps several times and the UPS performs a self test. See "Results of a
Self-Test" below. Note: you can leave connected equipment on during a
self-test. Your UPS, however, will not perform a self-test if the UPS is
not turned on (see "ON/OFF/STANDBY" Button description).