AVENTICS | PROFIBUS DP | R412009414-BDL-001-AE
Commissioning/Operation
S2
S1
Changing addresses
Both S1 and S2 rotary switches for the valve system station
address in the bus coupler are located beneath the PG fitting A.
O
Assign the station address freely from 2 to 99 using S1 and
S2:
S3
– S1: Unit digit from 0 to 9
– S2: Tens digit from 0 to 9
– S1 + S2 = station address
It is not possible to assign addresses twice within the bus
coupler
The set address is read in once from the bus coupler ASIC after
the supply voltage U
O
When making address changes, turn the bus coupler's
supply voltage off and then on again.
7.1.3
The S3 mode switch used to set the diagnostic messages is
located under the fitting A (see Figure on page 69).
When delivered, all switches are set to the OFF position.
The S3.6 switch is not assigned.
O
Set the necessary diagnostic messages using the S3 mode
switch (see Tab. 4).
The modified switch position will only be activated after a
new "power on".
has been switched on.
L

Setting diagnostic messages