AVENTICS | PROFIBUS DP | R412009414-BDL-001-AE
Commissioning/Operation
Calling up the diagnosis
7.2.3

Diagnosis with IndraWorks

The diagnosis under IndraWorks or the diagnostic display on the
bus coupler can provide you with information on potential
errors:
W
if the UL/DIA LED on the bus coupler is not lit permanently,
W
if one of the U
Q1
W
if a message appears in the bus master status display (see
"Reading the diagnostic display on the bus coupler" on
page 83).
O
To use the diagnosis in IndraWorks, click on the menu option
Ansicht, Diagnose (View diagnosis).
In addition to the Profibus standard diagnosis, the BDC-B-DP_32
module also sends a 7-byte user diagnosis.
The length of the data field is transferred in byte 1 (= 7) and the
user-specific diagnosis is transferred in byte 2. The meaning of
the bits is shown in Tab. 12. Bits 5-7 must have a value of 0.
Tab. 12:
Meaning of the bits in byte 2
Bit
Value
0
0
1
1
0
1
2
0
1
3
0
1
4
0
1
5
0
6
0
7
0
or U
LEDs is illuminated red or is off, or
Q2
Condition
-
Valve driver overload
-
12.5 V < U
< 21.6 V/20.4 V
Q1
-
12.5 V < U
< 21.6 V/20.4 V
Q2
-
U
< 12.5 V
Q1
-
U
< 12.5 V
Q2