The Class 2 wire-way at the top of the LMCP panel is designed to provide separation between Class 1 wiring and BACnet/IRB network
wiring. All 0–10V wires must originate as Class 2 or be reclassified. The 0–10V wires are routed through multiple 1.5" openings with
grommets in the top of the Class 1/Class 2 barrier. The BACnet/IRB wires are routed through the wire-way.
EMERGENCY LIGHTING WIRING WITH EM-IN EMERGENCY INTERIOR OPTION
0–10V AND NETWORK WIRING
0–10V
Line
Voltage
LMCP24-10V with EM-IN
Emergency Lighting
Neutral
Line
Emergency Power
Contractor Wiring
Factory Wiring
Neutral
Line
Normal Power
LM-MSTP Cable
LMRJ Cable
0-10V Dimming
Emergency Line
Power
Supply
NC
Contactor
EM-IN Emergency Interior
Coil
6
Wire-way
DIN-rail for
NB-ROUTER
mounting