Voltage And Circuit Protection; Important - Craftsman 919.184190 Manual Del Propietário

Ocultar thumbs Ver también para 919.184190:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

All manuals and user guides at all-guides.com
2.
The supply line should have the
same electrical characteristics
(voltage, cycle, phase) as the
motor. Refer to the motor
nameplate, on side of motor, for
this information.
NOTE: The supply voltage must be
the same as the motor nameplate
voltage plus or minus 10%. Refer to
local codes for correct wire size and
maximum wire run; undersize wire
causes high amp draw and
overheating of the motor.
Electrical wiring
must be located
away from hot surfaces such as
manifold assembly, compressor
outlet tubes, heads, or cylinders.
GROUNDING INSTRUCTIONS
This product should be connected to
a metallic, permanent wiring system,
or an equipment-grounding terminal
or lead on the product.
Grounding location is clearly
indicated on compressor.

Voltage and Circuit Protection

Refer to the Specification Table for
the voltage and minimum branch
circuit requirements.
IMPORTANT: This air compressor will
operate on a 15 amp circuit only if
the following conditions are met.
1.
Voltage supply through branch
circuit is 15 amps.
2.
Circuit is not used to supply any
other electrical needs (lights,
appliances, etc.).
D24917
3.
Circuit is equipped with a 15
amp circuit breaker or 15 amp
time delay fuse. NOTE: If
compressor is connected to a
circuit protected by fuses, use
only time delay fuses marked
"D".
If any of the above conditions cannot
be met, or if operation of the
compressor repeatedly causes
interruption of the power, it may be
necessary to operate it from a 20
amp circuit.
Air Distribution System
use with compressed air.
Regardless of its indicated
pressure rating, plastic pipe can
burst from air pressure. Use only
metal pipe for air distribution lines.
The next figure represents a typical
air distribution system. The following
are tips to remember when setting up
the air compressor's air distribution
system.
Use pipe that is the same size as
the air tank outlet. Piping that is
too small will restrict the flow of
air.
If piping is over 100 feet long,
use the next larger size.
Bury underground lines below
the frost line and avoid pockets
where condensation can gather
and freeze. Fill lines with air
pressure before covering to
make sure pipe joints are free
from leaks.
12- ENG
Plastic or PVC pipe
is not designed for

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido