ABB EOH361K Manual Del Usuario página 17

Ocultar thumbs Ver también para EOH361K:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Neutral assembly
Neutral assembly EOHXSN13
Neutral bus is included/factory mounted in service disconnects
EOH361/2/3NK -types. It is optional in EOH361/2/3K -types.
Install the neutral bus on the bottom plate of the safety switch
to the existing threaded holes according to the picture. See
chapter Cabling.
Wire range: #14 - 2/0, 2.5 - 70 mm
Safety
Torque: wire tightening
switch
Copper
size
[A]
[lbs.in]
[Nm]
30
35
3.9
60
45
5.1
100
50
5.6
2
Aluminium
[lbs-in]
[Nm]
40
4.5
45
5.1
50
5.6
Instruction Bulletin EOH361K/NK, EOH362K/NK, EOH363K/NK, 1SCC340029M1402 / B | Installation 1/13
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.