baltur TBG 35 Manual De Instrucciones página 6

Quemadores de gas monoestadio / biestadio
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 21
TECHNICAL SPECIFICATIONS
E
N
THERMIC CAPACITY
G
OPERATION
L
NOx EMMISION
I
FAN MOTOR
S
ABSORBED ELECTRICAL POWER*
H
IGNITION TRANSFORMER
POWER SUPPLY VOLTAGE
PROTECTION RATING
FLAME DETECTOR
NOISE**
WEIGHT
Methane Gas (G 20)
FLOW RATE
PRESSURE
*)
Total absorption at start with ignition transformer on.
**) Noise levels measured by the manufacturer in the laboratory with burner running on test boiler, at maximum nominal
thermal output.
STANDARD ACCESSORIES
BURNER COUPLING FLANGE
INSULATING GASKET
STUD BOLTS
HEXAGONAL NUTS
FLAT WASHERS
CONSTRUCTION CHARACTERISTICS
TBG 35
The burner consists of the following parts:
• Air intake with butterfly gate for the regulation of the air combust-
ing flow rate.
• Mounting flange to the sliding generator, to adapt the protuberance
of the head to various types of heating generators.
• Air pressure switch to ensure the presence of combustion air.
• Gas train complete with security valve and electromagnetic func-
tioning, minimum pressure switch, pressure regulator and gas filter.
• Flame detection by ionisation electrode.
• Automatic command equipment and burner control according to
European regulation EN298.
• Connection to gas train with fail safe connectors.
• 7 pole plugs for the electricity and thermostat supply of the burner.
• Preparation for the microammeter connection to the ionisation
cable.
• Electrical protection rating IP40.
MAX
kW
MIN
kW
One stage
mg/kWh
< 80 (Classe III secondo EN 676)
kW
r.p.m.
kW
26 kV - 40 mA - 230/240 V - 50/60 Hz
dBA
kg
MAX
m³n/h
MIN
m³n/h
MAX
mbar
CONSTRUCTION CHARACTERISTICS
TBG 35P
The burner consists of the following parts:
• Air intake with butterfly gate for the regulation of the air combust-
ing flow rate.
• Mounting flange to the sliding generator, to adapt the protuberance
of the head to various types of heating generators.
• Air pressure switch to ensure the presence of combustion air.
• Adjustment of air intake for the first and second stage by means
of electric servomotor.
• Gas train complete with security valve and one stage functioning,
and electromagnetic functioning, minimum pressure switch, pres-
sure regulator and gas filter.
• Flame detection by ionisation electrode.
• Automatic command equipment and burner control according to
European regulation EN298.
• Connection to gas train with fail safe connectors.
• 7 pole plugs for the electricity and thermostat supply of the burner,
4 pole plug for the command of the second stage of functioning.
• Preparation for the microammeter connection to the ionisation
cable.
• Electrical protection rating IP40.
4 / 18
0006081426_201003
TBG 35
TBG 35P
410
80
Two stages
0,37
2760
0,54
0,56
1N ~ 230 V ±10%- 50 Hz
IP 40
IONIZATION PROBE
76
40
41,23
8,05
360
TBG 35
TBG 35P
2
2
1
1
N° 4 M 12
N° 4 M 12
N° 4 M 12
N° 4 M 12
N° 4 Ø 12
N° 4 Ø 12

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbg 35 p

Tabla de contenido