Troubleshooting - Victron energy BlueSolar MPPT 70/15 Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4. Troubleshooting

Problem
Charger does not
function
Blown fuse
The battery is not
fully charged
The battery is being
overcharged
Load output does not
become active
6
Possible cause
Reversed PV connection
No fuse inserted
Reversed battery connection
A bad battery connection
Cable losses to high
Large ambient temperature
difference between charger
and battery (T
ambient_chrg
T
)
ambient_batt
Only for a 24V system: wrong
system voltage chosen (12V
instead of 24V) by the charge
controller
A battery cell is defect
Large ambient temperature
difference between charger
and battery (T
ambient_chrg
T
)
ambient_batt
Maximum current limit
exceeded
DC load in combination with
capacitive load (e.g. inverter)
applied
Short-circuit
Solution
Connect PV correctly
Insert 20A fuse
1.
Connect battery correctly
2.
Replace fuse
Check battery connection
Use cables with larger cross
section
Make sure that ambient
conditions are equal for charger
>
and battery
Disconnect PV and battery, after
making sure that the battery
voltage is at least >19V,
reconnect properly
Replace battery
Make sure that ambient
conditions are equal for charger
<
and battery
Make sure that the output
current does not exceed 15A
Disconnect DC load during start-
up of the capacitive load
Check for short-circuit in the
load connection

Publicidad

Tabla de contenido
loading

Tabla de contenido