10 Anexo
– X and Y values for the user defined linearization curve
curve_points_31_33
– X and Y values for the user defined linearization curve
curve status
– Result of table plausibility check
SUB_DEVICE_NUMBER
SENSOR_ELEMENT_TYPE
display_source_selector
– Selects the type of value, which is displayed on the indication and adjustment module
max_peak_sensor_value
– Holds the maximum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
min_peak_sensor_value
– Holds the minimum sensor value. Write access resets to current value. Unit derives from 'Sen-
sor_range.unit'
Calibration Highest Point
– Min./max.-adjustment: Upper calibrated point of the sensor. It refers to 'Cal_level_hi'. The unit
is defined in 'Sensor_range.unit'
Calibration Lowest Point
– Min./max.-adjustment: Lower calibrated point of the sensor. It refers to 'Cal_level_lo'. The unit
is defined in 'Sensor_range.unit'
cal_level_hi
– Min./max-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and 'Cal_type' = 1
(Online) the 'Cal_point_hi' is automatically set to the current sensor value. The unit is defined in
'Level_unit'
cal_level_lo
– Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1
(Online), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined
in 'Level_unit'
cal_type
– Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:
current sensor value determines 'Cal_point_hi/lo'
level
– Value after min./max.-adjustment
level_unit
– Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'
level_offset
– Offset that is added to the 'Level' value. Unit derives from 'Level_unit'
SENSOR_OFFSET
– Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'
end_of_operation_range
– Set up to suit the process conditions
begin_of_operation_range
– Set up to suit the process conditions
product_type
– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
liquids_medium_type
– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
solids_medium_type
– Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
62
VEGAPULS 67 • Foundation Fieldbus