.8.3 Technical data
Electrical
supply inlet
Model
DRD
230/3/60
265
460/3/60
230/3/60
325
460/3/60
230/3/60
400
460/3/60
230/3/60
500
460/3/60
230/3/60
700
460/3/60
230/3/60
800
460/3/60
230/3/60
1000
460/3/60
Calibration values
265-1000
Compressor
1
MC1(AC/Wc)
RLA
LRA
RLA
(A)
(A)
(A)
7.1
38
0.61
3.3
20
0.61
7.1
38
0.61
3.3
20
0.61
7.9
45
0.61
4.2
23
0.61
10
63
0.61
5
31
0.61
13.9
88
2.2
6.4
44
1.25
13.9
88
2.2
6.4
44
1.25
-
-
-
7.9
50
1.25
Hot gas valve
Fan pressure Switch
9-HGV
12-PV
ON: 261 PSIg
66.7 - 69.6 PSIg
OFF: 203 PSIg
4.6 - 4.8 barg
ON: 18 bar
OFF: 14 bar
Fan motor
Minimum circuit ampacity
3
MCA(Ac)
EV1 (Ac)
(HP)
(A)
0.59
8.9
0.59
4.8
0.59
8.9
0.59
4.8
0.59
9.9
0.59
5.6
0.59
12.5
0.59
7.0
1.07
19.5
1.07
9.3
1.07
19.5
1.07
9.3
-
-
1.07
11.1
High pressure switch
15-HP
406 PSIg
28 barg
Maximum protection device
rating
MCA(Wc)
HACR(Ac)
HACR(Wc)
(A)
(A)
(A)
-
10
-
6
-
10
-
6
-
15
-
10
-
15
-
10
17.4
20
8.0
15
17.4
20
8.0
15
-
-
9.9
15
Low pressure switch
6-LP
21.8 - 36.3 PSIg
1.5 - 2.5 barg
26
DRD265-1000
Minimum section
validated cable for
electrical
connections
Ø
-
12AWG
-
14AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
-
12AWG
-
14AWG
20
12AWG
15
12AWG
20
12AWG
15
12AWG
-
-
15
12AWG
Water pressostatic valve
22-WPV
232 PSIg
16 barg