WIKA FSD-3 Manual De Instrucciones página 20

Detector de caudal
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation
5.6 Adjustment
1. Depressurise the system and switch off the flow.
2
Mount the flow switch and connect it electrically.
.
(→ refer to chapter 5.1 "Mechanical mounting" and 5.2 "Electrical mounting")
3. Recall menu item "SETF" ▶ "MIN" and confirm "0".
EN
4. Set the maximum flow in the system.
Observe measuring ranges (→ see chapter 9 "Specifications").
5. Recall menu item "SETF" ▶ "MAX" and confirm "100".
5.7 Switching functions
Hysteresis function
If the flow rate fluctuates around the set point, the hysteresis keeps the
switching status of the outputs stable. With increasing flow rate, the output
switches when reaching the switch point (SP).
Contact normally open (HNO): Active
Contact normally closed (HNC): Inactive
With the flow rate falling again, the output will not switch back before the
reset point (RP) is reached.
Contact normally open (HNO): Inactive
Contact normally closed (HNC): Active
20
WIKA operating instructions flow switch, model FSD-3
Fig.: Hysteresis function

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido