Setting Maximum Ch Power; Setting Pump Setting; 7.5 Weather Dependent Regulation - Rotex GW-30 H12 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 260
7.3

Setting maximum CH power

The maximum CH power is set to 70% in the factory. If more power is required for the
CH installation, the maximum CH power can be changed by adjusting the rpm of the
fan. See table: Setting CH power.
This table shows the relation between the rpm of the fan and the unit power.
Desired CH power in kW (approx.)
RHOBG*AAV1
12
18
12.5
-
10.4
18.7
9.2
16.8
8.1
14.8
6.9
12.7
5.8
10.6
4.6
8.3
3.4
6.4
-
5.4
Caution:
The power is slowly increased when the fire is lit and is lowered when the set leaving
water temperature is reached (modulation on Ta).
7.4

Setting pump setting

The RHOBG**AAV1 CH boilers are fitted with a modulating A-class pump which modulates
on the basis fo the CH power provided. The minimum and maximum capacity of the pump can
be adjusted with the parameters 3 and c. Also see par. 7.2.
The set value of parameter 3. (max. pump setting) is the percentage of the maximum pump
capacity and is linked to the set maximum CH power as set with parameter 3
The set value of parameter c. (min. pump setting) is linked to the minimum CH-power as set
with parameter c
If the CH load modulates between the minimum and maximum value, the pump capacity will
modulate along proportionately.
Pressure loss graph unti CH side
A à RHOBG12AAV1 & RHOBG18AAV1
X à Flow over CH circuit in l/h
Y à Pressure loss / water head in mH
The minimum feedthrough amount
155 l/h
240 l/h
510 l/h

7.5 Weather dependent regulation

When connecting an outdoor sensor, the leaving water temperature is automatically
regulated dependent on the outdoor temperature, in accordance with the set fuel line.
The maximum leaving water temperature (T max) is set via the display. If so desired, the fuel
line can be changed by using the service code (see par.7.3).
Fuel line graph
X.
T outside in °C
Y.
T leaving water in °C
A.
Factory setting
(Tmax CH = 80°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
B.
Example
(Tmax CH = 60°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
Settings on service display
(in % maximum rpm)
100
85
80
70
60
50
40
30
25
O
2
5.4 kW
8.5 kW
17.8 kW
40

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gw-30 h18Rhobg12aav1Rhobg18aav1

Tabla de contenido