Resetting
Check the nature of the malfunction on the basis of the malfunction codes under par. 8.1 and if
possible, resolve the cause of the malfunction before resetting the unit.
If a locking malfunction is indicated by means of a flashing LED above the
number on the
display, the unit can be restarted by pressing the reset
7.2
Parameter settings via the service code
The parameters of the burner relay have been configured in the factory in accordance with the
following table.
These parameters can only be changed with the service code. Take the following actions to
activate the program memory:
1.
Press the
and the
2.
Use the
button to enter
3.
Use the
button to set the parameter you wish to configure, on the service display.
4.
Use the
and
button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the
The burner relay has now been reprogrammed.
Note
Pressing the
button will take you out of the menu without saving the parameter changes.
Example: Changing boiler from combi to 'hot domestic water only'
1.
Press the
and the
2.
Use the button to go to
3.
Press the
button 1 x. A 0 and a 1 will appear on the display.
4.
Use the
button to change the 0 to 2.
5.
Press the
button until
6.
The change has now been implemented. The unit will only respond to a hot water request.
Para
meter
Setting
0
Service code [15]
1
Installation type
2
CH pump continuous
3
Set maximum CH power
3.
Max. capacity modulating CH pump
4
Set maximum hot water power
5
Min. flow temperature of the heat line
5.
Max setting value supply water temperature
via operating panel
6
Min.outdoor temperature of the heat line
7
Max. outdoor temperature of the heat line
8
CH pump post-running time after CH
operation
9
CH pump post-running time after heating an
external DHW tank
A
Setting three-way valve
b
Booster
C
Step modulation
c
Minimum rpm CH
c.
Minimum capacity modulating CH pump /
Activation external power saving switch
0
button simultaneously, until a
15
(service code) on the temperature display.
button simultaneously.
15
.
P
appears.
RHOBG*AAV1
12
-
1
0
99
80
80
25
90
-7
25
1
0
0
0
1
30
40
button and a
button.
appears on the service display and a
P
button until
appears on the service display.
18
Description
-
Access to installers settings, the service code must be entered
(=15)
1
0= combi
1= heating and domestic hot water via external storage tank
2= domestic hot water only
3 = heating only
0
0= post-running pump only
1= pump continuously active
2-3-5= not active
85
Setting range value parameter c up to 85%
80
Setting range value parameter c. up to 100%
80
Setting reach set value parameter d up to 100% (=99 + 1x )
25
Setting reach 10°C to set value parameter 5
90
Setting reach 30°C to 90°C
-7
Setting reach -30 to 10°C
25
Setting reach 15°C to 30°C
1
Setting reach 0 to 15 minutes
0
Setting reach 0 to 15 minutes
(n/a for Combi unit)
0
0= powered during CH operation
1= powered during hot water operation and rest
2= three-way valve in CH setting if device not in rest
3= zone regulation
4 and higher = Not active
0
No active
1
0= step-by-step modulation off during CH operation
1= step-by-step modulation on during CH operation
30
Settings reach 20 – 50%
40
Setting range 0,15 – (value parameter c. )
0 = external power saving switch activated
0
on the temperature display.
38