Panasonic Urban Multi CS-20UMHPP Manual De Instalación Y Funcionamiento página 9

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 42
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and
I
the other to "SUB".
Main/sub changeover
1.
Insert a wedge-head screwdriver into the recess between the upper
and lower part of the remote controller and, working from the
2 positions, pry off the upper part.
(The remote controller PC board is attached to the upper part of
the remote controller.)
Turn the main/sub changeover switch on one of the two remote
2.
controller PC boards to "S". (See figure 20)
(Leave the switch of the other remote controller set to "M".)
1
Remote controller PC board
2
Factory setting
3
Only one remote controller needs to be changed
Computerised control (forced off and on/off operation)
1.
Wire specifications and how to perform wiring.
Connect input from outside to terminals T1 and T2 of the terminal
board (remote controller to transmission wiring).
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
Length
Contact that can ensure the minimum applicable load
External terminal
See
figure 19
1
Input A
2.
Actuation
The following table explains "forced off" and "on/off operations" in
response to input A.
Forced off
Input "on" stops operation
Input "off" enables control
3.
How to select forced off and on/off operation
Turn the power on and then use the remote controller to select
operation.
Set the remote controller to the field set mode. For details, refer
to the chapter "How to set in the field", in the remote controller
manual.
When in the field set mode, select mode No. 12, then set the first
code (switch) No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off at
factory set.)
(See figure 22)
1
Second code No.
2
Mode No.
3
First code No.
4
Field set mode
Centralized control
For centralized control, it is necessary to designate the group
I
No. For details, refer to the manual of each optional controller for
centralized control.
CS-20~125UMHPP
Urban Multi air conditioner
4PW12338-1A
(See figure 17)
2
0.75-1.25 mm
Max. 100 m
of 15V DC, 10mA
on/off operation
input off § on: turns on the unit
(impossible by remote controllers)
input on § off: turns off the unit
(by remote controller)
I
NSTALLATION OF THE DECORATION PANEL
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.
T
EST OPERATION
Refer to the installation manual of the outdoor unit.
The operation lamp of the remote controller will flash when an
I
error occurs. Check the error code on the liquid crystal display to
identify the trouble. An explanation of error codes and the
corresponding trouble are provided on "Caution for servicing" of
the indoor unit.
1
6
1
Drain pumping device (built-in) drain water is removed from the
room during cooling
2
Air flow flap (at air outlet)
3
Air outlet
4
Remote controller
Suction grill
5
Air filter (inside suction grill)
6
M
AINTENANCE
IMPORTANT
I
ONLY A QUALIFIED SERVICE PERSON IS ALLOWED TO
PERFORM MAINTENANCE.
I
BEFORE OBTAINING ACCESS TO TERMINAL DEVICES, ALL
POWER SUPPLY CIRCUITS MUST BE INTERRUPTED.
DO NOT USE WATER OR AIR OF 50°C OR HIGHER FOR
I
CLEANING AIR FILTERS AND OUTSIDE PANELS.
WHEN CLEANING THE HEAT EXCHANGER, BE SURE TO
I
REMOVE THE SWITCHBOX, FAN MOTOR AND DRAIN PUMP.
WATER
OR
DETERGENT
INSULATION OF ELECTRIC COMPONENTS AND RESULT IN
BURN-OUT OF THESE COMPONENTS.
2
3
5
4
4
MAY
DETERIORATE
THE
Installation and operation manual
7

Publicidad

Tabla de contenido
loading

Tabla de contenido