5.5. Outdoor installation

ATTENTION:
When the pump is to be installed outdoor, we recommend that the motor
is fitted under a rain cover.

5.6. Hot surfaces

DANGER:
When hot liquid is to be pumped, it must be ensured that people cannot
accidentally touch the equipment hot surfaces.
Figure 13 shows the parts in the pump that may get as hot as the hot liquid being
pumped.
Pump head
Pump sleeve
Pump base
Figure 13:
Pump hot surfaces
76
5.7. Fastening torques
The following table shows recommended fastening torque values for the stand and
flange bolts.
Model
Stand [N·m]
VF, VX, VN 1
40
VF, VX, VN 3
40
VF, VX, VN 5
40
VF, VX, VN 10
50
VF, VX, VN 15
50
VF, VX, VN 20
50
VF, VX, VN, VD 42
70
VF, VX, VN, VD 45
70
VF, VX, VN, VD 85
70
VF, VX, VN, VD 90
70
VF, VX, VN, VD 125
70
VF, VX, VN, VD 150
70
VF, VX, VN, VD 210
70
5.8. Flange forces and torques
The following table shows flanges' bolt maximum allowable forces and torques. If not
all loads reach the maximum permissible values, one of them may exceed the normal
limit.
Contact your distributor for more details.
Figure 14:

Flange strength and fastening torque

Direction Y: Inlet/outlet direction
Direction Z: Hydraulic body direction
Direction X: 90º from Inlet/outlet
Flange [N·m]
50-60
50-60
50-60
60-70
60-70
60-70
70-80
70-80
70-80
70-80
70-80
70-80
70-80
77