When Calling For Assistance; Installation Inspection - Briggs & Stratton Dual 200 Amp Manual Del Usuario

Ocultar thumbs Ver también para Dual 200 Amp:
Tabla de contenido

Publicidad

50 Amp Module
L2 IN
L2 OUT
L1 IN
G
A - Priority Selector
B - 50 Amp Relay
C - Relay Status LED
D - Signal Communication LED
E - Neutral Connection
F - Load Connection
G - Power/Line Connection
H - Ground Connection (optional)
J - Transparent, plastic cover
LED's are for signal communication status and relay position
status.
Utility power present:
• Normal State
Relay Position Status LED (C)
-
Green LED - Relay is closed; power available to appliance/
load
Signal Communication Status LED (D)
-
Orange LED - No communication and appliances/loads
cannot be managed by Symphony II System
• Problem State (see Troubleshooting)
Relay Position Status LED (C)
-
No LED - Power not available to managed appliance/load;
5 minute delay has not expired, verify correct wiring
-
Red LED - 50 Amp relay contacts in incorrect state;
replace 50 Amp module
22
NEUTRAL
NEUTRAL
L1 OUT
IN
OUT
F
E
J
Signal Communication Status LED (D)
A
-
No LED - No power to 50 Amp control board; verify
correct wiring
B
-
Green LED - Broken LED; replace 50 Amp module
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
C
Generator power present:
D
• Normal State
Relay Position Status LED (C)
-
Green LED - Relay is closed; power available to appliance/
load
-
No LED - Relay open, no power, Symphony II is
H
managing load
Signal Communication Status LED (D)
-
Green LED - Signal communication detected and
appliances/loads are being managed after 5 minute delay
• Problem State (see Troubleshooting)
Relay Position Status LED (C)
-
No LED - Power not available to managed appliance/load;
5 minute delay has not expired, verify correct wiring
-
Red LED - 50 Amp relay contacts in incorrect state;
replace 50 Amp module
Signal Communication Status LED (D)
-
No LED - No power to 50 Amp control board; verify
correct wiring
-
Orange LED - Signal communication not detected; verify
correct wiring
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires

When Calling for Assistance

You must have the Model Number and Serial Number from each
transfer switch or remote module ID label at hand if it is necessary
to contact a local service center regarding service or repair. Obtain
this information from the unit ID labels located on or inside device.
For convenience, record the information on the inside front cover of
this manual.
To contact Briggs & Stratton call 800-743-4115, between 8:00 AM
and 5:00 PM CT.

Installation Inspection

Before placing the system into service, inspect the entire installation
carefully.
This completes the installation and startup instructions. The
operator's manual provides full details on Operation, Maintenance,
and Troubleshooting for the Automatic Transfer Switch.