REMS Multi-Push S Instrucciones De Servicio página 31

Ocultar thumbs Ver también para Multi-Push S:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 63
eng
5.2 Fault: Compressor will not start although there is low or no pressure in the compressed air tank (see the display on the compressed air tank pressure gauge
(Fig.4 (30)).
Cause:
Compressor emergency stop button (Fig.4 (29)) is switched off.
REMS Multi-Push defective.
5.3 Fault:
Cause:
Stop tap of the house connection is only partly open.
Not enough tapping points opened.
Hoses connected incorrectly.
Wrong defaults entered.
Valves blocked, considerable, irremovable encrustations in the pipes.
5.4 Fault: The set pressure (p refer) is not reached in the test with compressed air or compressed air pump programs (REMS Multi-Push SL/SLW).
Cause:
Installation or compressed air hose (Fig. 4 (23)) leaking.
No or too little pressure in the compressed air tank.
REMS Multi-Push defective.
5.5 Fault: The set pressure (p refer) is not established in the test with water program (Multi-Push SLW).
Cause:
The water pressure of the house connection is greater than the set pressure
(p refer).
Suction/pressure hose (Fig. 1 (13)) or high-pressure hose (Fig. 4 (26)) leaking.
Hydro-pneumatic pump does not build up pressure.
Stop tap of the water supply is closed or only partly open.
No or too little air pressure in the compressed air tank.
REMS Multi-Push defective.
5.6 Fault: The pressure in the pipe to be tested is not relieved after running the test with water programs or during the test with water B, P+M (REMS Multi-Push SLW).
Cause:
Pressure relief water drain (Fig. 4 (27)) is soiled or defective.
REMS Multi-Push defective.
5.7 Fault: No or not enough ingredient is injected from the bottle.
Cause:
Unsuitable disinfectant, cleaning, preserving agent.
REMS V-Jet TW or REMS V-Jet H connected wrongly to the Multi-Push.
REMS V-Jet TW or REMS V-Jet H soiled.
REMS V-Jet TW or REMS V-Jet H defective.
5.8 Fault: The date and time must be reset every time the REMS Multi-Push is switched on.
Cause:
Battery depleted.
5.9 Fault: The new version software was not installed.
Cause:
USB stick not recognised.
New version software is not on the USB stick.
The USB stick was pulled out of the USB port
(Fig. 2 (33)) during the installation.
A folder was created on the USB stick and the new version software was
copied into this folder.
5.10 Fault:
Cause:
The font "Lucida Console" is required for a correct display.
5.11 Fault: Printing on paper weak or illegible. Printout aborted prematurely.
Cause:
Weak battery charge.
Paper reel inserted incorrectly in printer.
The printer can only be used as of Version Software 2.0.
5.12 Fault: "Error" is displayed on the screen (6).
Cause:
A fault has occurred.
Switch on compressor by pulling out the emergency stop button.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
Fully open the stop tap.
Open the appropriate number of tapping points.
Connect hoses as shown in Fig. 3.
Check defaults, correct if necessary. Restart the program.
Clean/change valve(s). Clear encrustations.
Check installation for leaks. Change the compressed air hose.
See 5.2 Fault:
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
Close the shut-off valve of the house connection.
Change suction/pressure hose or high-pressure hose.
Connect suction/pressure hose between the house connection and the
pressure test with water supply, see 2.6.2.
Fully open the stop tap.
Hydro-pneumatic pump requires compressed air, see 5.2 Fault:
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
or an authorised REMS customer service workshop.
Have the REMS Multi-Push checked/repaired by an authorised REMS
customer service workshop.
Use REMS Peroxi Color, REMS CleanH, REMS NoCor.
Clean REMS V-Jet TW or REMS V-Jet H, see also 4.1.
Have REMS V-Jet TW or REMS V-Jet H checked/repaired by authorised
REMS customer service workshop.
Use REMS V-Jet H exclusively for REMS CleanH cleaner and REMS NoCor
corrosion protection.
Change battery. See 4.1.
Use another USB stick.
Copy new version software to the USB stick.
Repeat the procedure described in 2.3.. Use a USB stick with a LED if
possible.
Move the new version software into the main directory of the USB stick.
Select font "Lucida Console", install if necessary.
Charge battery.
Insert paper roll, see 3.8.
Unplug REMS Multi-Push. Remove all hoses, caps and stoppers. Then restart
REMS Multi-Push. If "Error" still appears, have the REMS Multi-Push checked/
repaired by an authorised REMS customer service workshop.
eng
31

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Multi-push slMulti-push slw

Tabla de contenido