Heronhill - for all your Toshiba requirements
All manuals and user guides at all-guides.com
G
Install the Noise Filter Kit either inside indoor unit No. 2 or within 0.5m of the electrical box of indoor
unit No. 2.
G
From the PCB in indoor unit No.2 remove the T A Sensor from CN04.
G
Replace the T A Sensor with the 0.5m extension lead into CN04.
G
Connect the other end of the 0.5m extension lead into the input socket PJ-B of the noise filter.
G
Connect the 12m extension lead to the output PJ-A of the noise fiilter and route the 12m extension
lead to indoor unit No. 1. Do not cut this cable, coil any excess cable safely.
G
When routing the 12m cable, care should be taken to ensure that it is not in direct contact with mains
cable or routed in duct or conduit containing power cables.
G
Fix the sensing tip of the T A Sensor removed from indoor unit No.2 with the cable ties supplied, to the
sensing tip of the T A Sensor in indoor unit No.1 on its support post so that they are both positioned in
the air stream.
G
Connect the male plug on the end of the 12m extension lead from the noise filter to the female plug of
the repositioned T A Sensor, ensuring that any spare lead is safely coiled.
Indoor Unit 1
T A Sensor
Unit 1
T A Sensor
Unit 2
(repositioned)
Twin Kit Pack Contents
Quantity
Item
1
1
2
1
3
1
4
1
5
6
6
1
7
2
Tel: 01823 665660
C
O
T
OOLING
NLY
WIN
12m Extension
Cable
(Item -4)
Male/Female
Plug & Socket
Description
RBC-TK45ESCO – Twin kit in metal enclosure
Filter Kit – Black ABS enclosure
0.5m Extension Lead – Connects CN04 (I/D No.2 PCB) to PJ-B (Filter Kit)
12m Extension Lead – Connects PJ-A (Filter kit) to T A Sensor (I/D No. 1)
12.7mm x 6mm Pan head self-tapping screws
Instruction Leaflet
Cable Ties
~ 37 ~
www.heronhill.co.uk
K
S
U
IT
ET
P
0.5m Extension
Cable (Item -3)
Noise Filter
Kit
(Item -2)
Fax: 01823 665807
GB
Indoor Unit 2