Annex 5, sheet 2, of the General Construction Inspection Approval
no. Z-40.21-432 of the 17th October 2008
Table 1: Reference dimensions for the insertion depth of the limit
detector for a series installation
Tank
Number
Diameter
type
of Tanks
of the back
pressure
nozzle (mm)
1
2
3
1500
4
5
**
taken from the report of TÜV North, Plant Technology, of the 6th March
2001 under file: 111 BG Roth
Table 2: Reference dimensions for the insertion depth of the limit
detector for an end-to-end installation with filling system
„Füllstar M"
Tank
Number
Diameter
type
of Tanks
of the back
pressure
nozzle (mm)
2
1500
**
taken from the report of TÜV North, Plant Technology, of the 2nd March
2006 under file: 8237 BM 00160
It must be ensured that, under repeated filling conditions, the filling level
difference between the containers does not exceed 100 mm.
5
Connecting pipelines
(1) When connecting pipelines to the container connecting union,
ensure that undue force is not required and that no additional
external stresses result which then act on the container in an
unintended manner.
(2) If a fixed pipeline is connected to the container, it must satisfy
the requirements of TRbF and withstand a test pressure of 10 bar.
(3) Flushing- and ventilation lines must conform to TRbF 20
9.1.2, must have adequate dimensions and must not be able to
be blocked. They and their pipeline connections must be set up so
that they remain leak proof with 0.3 bar overpressure.
Several containers may be -connected to the same flushing and
ventilation pipeline, only if the liquids they will store and their
vapours will not combine to produce dangerous compounds.
Lines- and equipment for flushing and ventilating must not
discharge into closed spaces.
The outlet openings must be protected from rainwater ingress.
9
Technical regulations for combustible liquids, TRbF 50;
June 2002 Edition Pipelines
10
TRbF 20, May 2002 version; Technische Regeln für brennbare
Flüssigkeiten, Läger ("Technical Regulations for Combustible Liquids,
Storage Rooms")
Reference dimension**
for the limit detector
(measured from the
topedge of the container
connector)
(mm)
12
295
12
270
12
260
12
265
12
270
Reference dimension**
for the limit detector
(measured from the
topedge of the container
connector)
(mm)
12
285
no.
10
GB
15