Daikin FXMQ20PAVE Manual De Instalación página 16

Ocultar thumbs Ver también para FXMQ20PAVE:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Table 4
MODE NO.
FIRST CODE NO.
11 (21)
SECOND CODE NO.
01
OFF
airflow adjustment
(4) After the air conditioner stops operating, check with
"MODE NO. 21" on an indoor unit basis that 02 is set
for the "SECOND CODE NO." in Table 4. If the air
conditioner does not stop operating automatically or
the "SECOND CODE NO." is not 02, repeat steps
from (3). If the outdoor unit is not turned ON, U4 or
UH as explained in Table 8 will be displayed. This
display is not problematic, because this function is
set for the indoor unit. Continue setting the function.
After setting this function, be sure to turn ON the
outdoor unit before the test operation of the outdoor
unit. If any other error is displayed, refer to Table 8
and the operation manual provided with the outdoor
unit and check the defective point.
CAUTION
• If there is any change after airflow adjustment in the
ventilation paths (e.g., the duct and air outlet), be sure to
make airflow auto adjustment again.
• Consult your Daikin representative if there is any change
in the ventilation paths (e.g., the duct and air outlet) after
the test operation of the outdoor unit is finished or the
air conditioner is moved to another place.
(b) Select External Static Pressure with Remote Controller
Check that 01 (OFF) is set for the "SECOND CODE NO."
in "MODE NO. 21" for airflow adjustment on an indoor
unit basis in Table 4. The "SECOND CODE NO." is set to
01 (OFF) at factory set. Change the "SECOND CODE
NO." as shown in Table 5 according to the external static
pressure of the duct to be connected.
(1) The "SECOND CODE NO." is set to 07 (an external
static pressure of 100 Pa) at factory set. (FXMQ40 ·
50 · 63 · 80 · 100 · 125 · 140)
The "SECOND CODE NO." is set to 02 (an external
static pressure of 50 Pa) at factory set. (FXMQ20 · 25
· 32)
*1 The FXMQ50 · 63 · 80 · 100 · 125 cannot be set
to 30 Pa.
*2 The FXMQ40 cannot be set to 180 or 200 Pa.
*3 The FXMQ20 · 25 · 32 cannot be set to
110-200 Pa.
*4 The FXMQ140 cannot be set to 30 Pa and
150-200 Pa.
14
Setting contents
Airflow
7
adjustment
02
03
Completion of
Start of airflow
adjustment
Table 5
External Static
MODE NO.
Pressure
30Pa (*1)(*4)
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
110Pa (*3)
13 (23)
120Pa (*3)
130Pa (*3)
140Pa (*3)
150Pa (*3)(*4)
160Pa (*3)(*4)
180Pa
(*2)(*3)(*4)
200Pa
(*2)(*3)(*4)
CAUTION
Keep in mind that a shortage of airflow quantity or water leakage
will result because the air conditioner will be operated outside
the rated range of airflow quantity if the external static pressure
is wrongly set.
3. Filter Sign Settings
• The remote controller is provided with an LCD that tells
the time of air filter cleaning.
• If the air conditioner is used in places with excessive dust,
change the "SECOND CODE NO." as shown in Table 6.
The "SECOND CODE NO." is set to 01 (standard) at
factory set.
Table 6
Time for
Dirt
display
Approximately
Standard
2500 hours
Excessive
Approximately
dust
1250 hours
N
o
d
s i
l p
y a
(
) *
* Select "No display" under conditions in which the cleaning
display is not required, such as the time of regular maintenance.
4. Switching time of the dry operation at VRTsmart control
setting.
• If you change the operation mode to "Dry" when
VRTsmart control is in effect, the operation mode is
change to "Cooling" after certain period of time.
If you want to continue dry operation longer, please change
the setting position as mentioned in the table below.
(Setting position of factory setting is "0".)
If you keep dry operation longer, energy saving
performance decrease.
Mode
Dry operation
number
30 min
60 min
10
90 min
Continuous (Not return
to Cooling)
At the time of Group control setting, Dry operation time for
the indoor units in the same group shall be the same
setting value.
FIRST
SECOND
CODE NO.
CODE NO.
01
02
03
04
05
06
07
08
06
09
10
11
12
13
14
15
MODE
FIRST
SECOND
NO.
CODE NO.
CODE NO.
01
0
10 (20)
02
3
Setting switch
Setting position
number
number
01
02
10
03
04
English