Indoor Unit Installation - Daikin FXMQ20PAVE Manual De Instalación

Ocultar thumbs Ver también para FXMQ20PAVE:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

• FXMQ20 • 25 • 32 • 40 type
700
631
(Hanging bolt pitch)
Air outlet
Bottom of unit
Hanging bolt (× 4)
Fig. 2-2
Case 2, 3
Inspection hatch
(Ceiling opening)
Inspection hatch
Inspection hatch 1
(450×450)
Control box
Inspection
hatch 2
7
0
0
(Same as the
indoor unit
size or more)
Axial direction view A-1
• Determine the H3
dimension by maintaining a
downward slope of at least
1/100 as specified in
"7. DRAIN PIPING WORK".
(2) Mount the canvas ducts to the air outlet and inlet so that the
vibration of the air conditioner will not be transmitted to the
duct or ceiling. Apply a sound-absorbing material (insulation
material) to the inner wall of the duct and vibration insulation
rubber to the hanging bolts (refer to 8. DUCT WORK).
(3) Open installation holes (if the ceiling already exists).
• Open the installation holes on the ceiling. Lay the
refrigerant piping, drain piping, power line, transmission
wiring, and remote controller wiring for the piping and
wiring connection port of the unit.
In the case of the installation of a wireless remote
controller, refer to the installation manual provided with
the wireless remote controller.
Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN
PIPING WORK, and 10. WIRING EXAMPLE AND HOW
TO SET THE REMOTE CONTROLLER.
• The ceiling framework may need reinforcement in order
to keep the ceiling horizontal and prevent the vibration of
the ceiling after the installation holes are opened. For
details, consult your construction or interior contractor.
English
Inspection hatch 1
(450×450)
Control box
Air inlet
Inspection hatch 2
(450 x 450)
(For remove drain pan and change part)
* In case can work at space of below
product, inspection hatch 2 is
unnecessary.
Control box
A
Ceiling
Inspection hatch 3
(Same as the indoor
unit size +300 or more)
Control box
7
0
0
Axial direction view A-2
Fig. 2-3
Model
B
C
20 • 25 • 32 type
550
588 850
40 type
700
738 1000
50 • 63 • 80 type
1000 1038 1300
100 • 125 • 140 type
1400 1438 1700
(length: mm)
(4) Install the hanging bolts. Make sure that the hanging bolts
are M10 in size.
• Use hole-in anchors if the hanging bolts already exist;
otherwise use embedded inserts and embedded
foundation bolts so that they will withstand the weight
of the unit.
Adjust the distance to the ceiling surface in advance.
Installation example
Note) All the above parts are field supplied.

5. INDOOR UNIT INSTALLATION

〈It may be easier to install accessories (sold separately)
before installing the indoor unit. Refer to the installation
manuals provided to the accessories as well.〉
Be sure to use the accessories and specified parts for
installation work.
(1) Temporally install the indoor unit.
• Connect the hanging brackets to the hanging bolts. Be
sure to use and tighten the nut and washer (11) for each
hanging bracket from both upper and lower sides of the
hanging bracket. (Refer to Fig. 3) At that time, the fall of
the washer (11) for the hanging bracket can be
prevented if the washing fixing plate (9) is used.
[Fixing hanging brackets]
D
[Fixing method of washers]
Insert
Washer fixing plate (9)
(accessory)
CAUTION
• During the installation work, perform the curing of the air
outlet and protect the resin drain pan of the indoor unit
from the intrusion of foreign substances, such as
welding spatters.
Otherwise, water leakage may occur as a result of damage,
such as hole damage, to the resin drain pan.
Ceiling slab
Anchor
Long nut or turn-buckle
Hanging bolt
Indoor unit
Part to be procured in the field
Washer (11) (accessory)
Tighten from above and below
(Double nut)
Nut on the upper side
Fig. 3
5

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido