NOTE
For VRTsmart control function it is necessary to connect with
an outdoor unit with a compatible function.

12. TEST OPERATION

Refer to the installation manual of the outdoor unit.
• The operation lamp of the remote controller will flash when
an malfunction occurs. Check the malfunction code on the
liquid crystal display to identify the point of trouble. An
explanation of malfunction codes and the corresponding
trouble is provided in "CAUTION FOR SERVICING" of the
outdoor unit. If any of the items in Table 8 are displayed,
there may be a problem with the wiring or power, so check
the wiring again.
Table 7
Remote controller display
"A8" lit
"C1" lit
"C6" lit
"U3" lit
Table 8
Remote control display
"
" is lit up
"U4" is lit up
"UH" is lit up
No display
CAUTION
If interior finish work is continuing on completion of the test
operation of the air conditioner, explain the customer not to
operate the air conditioner until the interior finish work is
completed for the protection of the air conditioner.
Otherwise, substances that will be generated from interior finish
work materials, such as paint and adhesive agents, may
contaminate the air conditioner.
English
Contents
Error in power supply voltage to
indoor unit.
Fan driver PCB of indoor unit ↔
indoor control PCB transmission
error.
Improper combination of fan driver
PCB of indoor unit or setting failure
in control PCB type.
Test operation of outdoor unit has
not been finished.
Content
• There is a short circuit at the
FORCED OFF terminals (T1, T2)
• The power on the outdoor unit is
off.
• The outdoor unit has not been
wired for power supply.
• Incorrect wiring for the transmis-
sion wiring and / or FORCED OFF
wiring.
• The power on the indoor unit is
off.
• The indoor unit has not been
wired for power supply.
• Incorrect wiring for the remote
controller wiring, the transmission
wiring and / or the FORCED OFF
wiring.

13. WEIGHT AND DIMENSION

Model
FXMQ20
25
32
FXMQ40
FXMQ50
63
80
FXMQ100
125
FXMQ140
Width
Length
Height
Weight
(mm.)
(mm.)
(mm.)
(kg.)
700
550
300
25
700
700
300
27
700
1,000
300
35
700
1,400
300
45
700
1,400
300
46