9.4

Temperature regulation with external probe connected.

9.4.1
With On/Off type ambient thermostat
It is possible to OFFSET the curve by rotating the heating knob. The curve offset causes a variation of the setpoint of the climate
curve in relation to the original value. See the previous chart (figure BO-0000056) for the selection of the curve (the example
shown refers to a 1.5 curve). The OFFSET adjustment range is between 5 and 30, with a factory value set to 20 (figure BO-
0000152). Each OFFSET variation degree corresponds to a temperature adjustment of 2.5 °C of the set curve heating setpoint.
CP000
80
75
OFFSET 30
70
65
60
55
50
45
40
35
30
25
CP210
20
20
15
10
5
9.4.2
With modulating type ambient unit
When the boiler is connected to a modulating type ambient unit, climatic curves are disabled. In this case, the
to set the maximum heating delivery temperature. To set the new climate curve, see the instructions supplied with the ambient
accessory installed.
9.5

Reading out measured values

Press the button
to view information on operation of the boiler.
• press the button for 1 second to view the work mode (for example: "t.17" = Venting function being completed).
• press the button again for 1 second to view the operating sub-status or the relative work function (for example: "u.00" = Boiler
in stand-by).
• press the button again for 1 second to view the operating temperature for heating: the symbol
value in °C then appears.
• press the button again for 1 second to view the operating temperature for DHW: the
temperature value in °C appears.
• press the button again for 1 second to view the power level between 0 and 100: the
appears.
• Press again for 1 second: the symbols
• Press again for 1 second: the symbols
• Press again for 1 second: the symbols
To exit, press and hold the
The energy consumption values of the meters, in kWh, are purely indicative.
7696306 (01-12/17)
CP230
1,5
OFFSET 20
OFFSET 5
0
-5
-10
-15
-20
Te
(°C)
and the meter for energy consumption (kWh) in heating mode appear.
and the meter for energy consumption (kWh) in DHW mode appear.
and the meter for cooling x.x.x (NOT USED) appear.
button for more than 3 seconds.
OFF
-25
-30
38
20°
30°
OFF
MAX
RESET
BO-0000152
knob is used
flashes and the temperature
symbol flashes, followed by the
symbol flashes and the power level