Installation

5.1

Select location

Requirement(s):
ü Technical data and mains data are the same.
1 "4 Technical data" [} 14]
ü Permissible ambient conditions are observed.
ü The product and the charging station are in suf-
ficient proximity to each other, depending on
the length of the charging cable used.
ü The following minimum clearances to other ob-
jects (e.g. walls) must be complied with:
n Distance to left and right: 300 mm
n Distance above: 300 mm
ü Connection to a backend system: The mobile
network is fully available at the location.
ü If several products are to be networked, they
must be in sufficient proximity to each other.
The length of an Ethernet cable must be no
longer than 100 m.

5.1.1 Permissible ambient conditions

DANGER
Risk of explosion and fire
If the product is operated in potentially explosive
areas (ex areas), explosive substances may be ig-
nited by sparking of product components. There is
a risk of explosion and fire.
u Do not use the product in potentially explosive
atmospheres (e.g. gas filling stations).
16
ATTENTION
Material damage due to unsuitable ambient con-
ditions
Unsuitable ambient conditions can damage the
product.
u Protect the product from a direct water jet.
u Avoid direct sunlight.
u Ensure adequate ventilation of the product. Ad-
here to minimum distances.
u Keep the product away from heat sources.
u Avoid large temperature fluctuations.
Permissible ambient conditions
Ambient temperature [°C]
Average temperature over 24
hours [°C]
Altitude [m above sea level]
Relative humidity (non-con-
densing) [%]
5.2

Preparatory work on site

5.2.1 Upstream electrical installation

The tasks described in this section may only
be carried out by a qualified electrician.
DANGER
Fire hazard due to overload
If the upstream electrical installation is flawed (e.g.
supply line), there is a fire hazard.
u Design the upstream electrical installation ac-
cording to the applicable regulatory standards
and the technical data and configuration of the
product.
1 "4 Technical data" [} 14]
Min.
Max.
-30
+50
+35
2,000
95