4. Piping Installation

4.1 Recommended Piping Diameters

Based on the proposed piping layout and the actual locations of both the In-Row Cooler and the condenser, calculate the total
equivalent piping distance, including bends and traps, to determine the necessary piping diameters.
Note: For equivalent piping length longer than 100 ft. (30 m), use the long piping kit (SRCOOLLONGPKIT).
Look up the recommended piping diameters for both the discharge and liquid piping using the Table: Recommended Piping
Diameters.
Table: Recommended Piping Diameters (Use Type L ACR Copper Tubing)
Equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Note: Installations at distances greater than 30 m (100 ft.) require using the Long Pipe Kit (SRCOOLLONGPKIT).
Equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Maximum equivalent length
SRCOOLDXRW12
SRCOOLDXRW25
Note: For equivalent distance greater than 32.5 ft., the vertical discharge piping is generally one size smaller than the horizontal to improve
velocity.
Discharge horizontal
5/8"
7/8"
5/8"
7/8"
3/4"
7/8"
3/4"
1"
7/8"
1"
7/8"
1"
14
Discharge vertical
0 to 32.5 ft. (0 to 10 m)
5/8"
7/8"
32.5 to 65 ft. (10 to 20 m)
5/8"
7/8"
65 to 100 ft. (20 to 30 m)
5/8"
3/4"
100 to 130 ft. (30 to 40 m)
5/8"
7/8"
130 to 165 ft. (40 to 50 m)
3/4"
7/8"
165 to 200 ft. (50 to 60 m)
3/4"
7/8"
Liquid line
1/2"
1/2"
1/2"
1/2"
1/2"
5/8"
5/8"
5/8"
5/8"
5/8"
5/8"
3/4"