Placement Clearance - Tripp-Lite SRCOOLDXRW12 Manual De Instalación

Ocultar thumbs Ver también para SRCOOLDXRW12:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2. In-Row Cooler Installation

2.3 Placement Clearance

Using its casters, install the In-Row Cooler beside a rack enclosure. Ensure the installation area has sufficient clearance for
both airflow and maintenance and repair. Refer to Figure 2-3: Installation Clearance Requirements below.
48 in.
(1200 mm)
39.4 in.
(1000 mm)
Figure 2-3: Installation Clearance Requirements
If installing the cooling unit at the end of a row, a minimum of 19 in. (460 mm) clearance is needed on the side for servicing.
Adjust the leveling feet to ensure the entire unit is level for proper condensate drainage.
Secure the unit directly to the adjacent rack enclosure using baying brackets. For installation next to Tripp Lite racks, use the
Z-shaped baying brackets included with the cooler. Refer to Protruded (left) and Flush (right) installation diagram below.
Figure 2-4: Protruded (left) and Flush (right) installation
6

Publicidad

Tabla de contenido
loading

Tabla de contenido