Condenser Installation; Condenser Elevation; Attach Supplied Lifting Brackets; Lifting Crane - Tripp-Lite SRCOOLDXRW12 Manual De Instalación

Ocultar thumbs Ver también para SRCOOLDXRW12:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Condenser Installation (Outdoor Unit)
Note: Avoid installing the condenser in areas with excess heat, dust or debris. Refer to local codes and regulations for proper reinforcement
for high wind areas. The maximum outdoor operating temperature is 110ºF (43ºC).
3.1 Condenser Elevation and Distance
Confirm that the vertical distance between the condenser and In-Row Cooler is within the range listed in the Condenser
Elevation Installation Limits table.
Take measurements from the bottom surface (excluding legs) of the condenser to the bottom surface of the In-Row Cooler.
Table: Condenser Elevation Installation Limits
Type
Positive (condenser higher than indoor unit)
Negative (condenser lower than indoor unit)
3.2 Attach Supplied Lifting Brackets and Screws to Condenser
Note: After removing the lifting brackets, save the screws; they will be used to attach the condenser's legs at a later time (refer to section
3.4 Condenser Leg Installation for more information).

3.3 Lifting Crane

If the condenser will be installed on a rooftop, a lifting crane may be required.
Figure 3-1: Attach Supplied Lifting Brackets and Screws to Condenser
Figure 3-2: Example of Lifting the Condenser
Vertical height value
Max: +65 ft. (20 m), bottom-to-bottom
Max: -16 ft. (-5 m)
7