2. In-Row Cooler Installation
• For maximum cooling performance in humid environments, install vapor barriers on walls and floors to ensure the cooler is generating the
highest amount of sensible vs. latent cooling.
• This product is rated for 64.0 to 98.6°F (17.7 to 37°C), 20 to 80% RH indoor temperature and 14 to 95°F (-10 to 35°C) outdoor
temperature. The system continues operating when the outdoor temperature is up to 113°F (45°C), but at reduced cooling capacity and
efficiency. The system is protected for temperatures above 113°F (45°C). Contact the manufacturer if over range.
Minimum/maximum air temperature test was conducted at 55°F (12.8°C) indoor temperature and 5°F (-15°C) outdoor temperature /
116.6°F (47°C) indoor temperature and113°F (45°C) outdoor temperature for cooling mode.
• GWP for R410A (R32/125: 50/50): 2087.5.
2.1 Unpacking
Refer to the unpacking guide attached to the outside of the In-Row Cooler container.
Note: Retain the shipping brackets attached to the In-Row Cooler if installation will be anchored to the floor.
2.2 Side Air Discharge
CAUTION: Remove front airblock (if installed flush) or install perforated side panels (if installed protruded)
before turning on the In-Row Cooler. Failure to do so will result in damage to the In-Row Cooler.
The In-Row Cooler ships with both the solid front door airblock and the solid side discharge panels pre-installed. Configure the
air discharge according the following table.
Table: Air Discharge Configurations
Front of In-Row Cooler Alignment
Flush, front-only discharge
Protruded, side-only discharge
Protruded, front and side discharge
Figure 2-1: Perforated side panels installed, front airblock installed.
Front Door Airblock
Removed
Installed
Removed
Figure 2-2: Solid side panels installed, front airblock removed.
5
Side Airblock Type
Solid panels
Perforated panels
Perforated panels