Condensate Drainage - Tripp-Lite SRCOOLDXRW12 Manual De Instalación

Ocultar thumbs Ver también para SRCOOLDXRW12:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Piping Installation
Table: Equivalent Length of the Sub-Assembly with the Following Piping Turns/Angles
Piping Diameter (in.)
3/8
1/2
5/8
3/4
7/8
1
1-1/8

4.2 Condensate Drainage

Ensure there is access to a nearby water drain for the condensate management system.
The In-Row Cooler comes preinstalled with a condensate management system and ships with condensate tubing.
Connect the drain tube to the In-Row Cooler (see Table: Drain connection information) from either the top or the bottom.
Table: Drain connection information – SRCOOLDXRW12, SRCOOLDXRW25
Connection Size
Drain Tube Length
Max Flow
Maximum Lift
Maximum Distance
*Note: 1 foot of lift equals 10 feet of distance.
• Pitch the discharge piping down and away from the In-Row Cooler at a decline of 1 in. per 10 ft. (10 mm per 1 m)
• Ensure not to expose the drain tube to freezing temperatures
• Perform a test with water to ensure the drainage system is working properly
Elbow 90°
0.7 ft. (0.21 m)
0.8 ft. (0.24 m)
0.9 ft. (0.27 m)
1 ft. (0.3 m)
1.4 ft. (0.44 m)
1.6 ft. (0.5 m)
1.8 ft. (0.56 m)
1/4 in.
13 ft. (4 m)
2.4 gal/h (9 L/h)
26.5 ft. (8 m)*
150 ft. (45 m)*
15
Equivalent Length
Elbow 45°
0.3 ft. (0.1 m)
0.4 ft. (0.12 m)
0.5 ft. (0.15 m)
0.6 ft. (0.18 m)
0.8 ft. (0.24 m)
0.9 ft. (0.27 m)
1 ft. (0.3 m)
T-Piece
2.5 ft. (0.76 m)
2.5 ft. (0.76 m)
2.5 ft. (0.76 m)
2.5 ft. (0.76 m)
3.6 ft. (1.1 m)
4.1 ft. (1.25 m)
4.6 ft. (1.4 m)

Publicidad

Tabla de contenido
loading

Tabla de contenido