Number Of Compressors Settings; Maximum Pressure Alarm Settings - Ingersoll Rand System Automation X4I Manual De Configuración Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 77

NUMBER OF COMPRESSORS SETTINGS

1. From the S02 home screen, scroll up (+)
or scroll down (-)
highlight 02- NC (Number of Compressors).
Number of Compressors Settings
2. The default setting for this parameter is 4. The 4
indicates the number of compressors the X4I is
configured for and the number of compressors
that will be sequenced by the X4I. This value
must be set to match the system at
commissioning.
3. Press the enter
Number of Compressor configuration screen.
The flashing cursor should be displayed
highlighting the Number of Compressor
parameter. The values for this parameter are "1"
to "4".
4. Scroll up (+)
until the value matches the number of
compressors that you have wired into the
controller. Press the enter
confirm your selection.
5. You should be returned to the S02 home screen
and values just entered should appear next to
the NC parameter.

MAXIMUM PRESSURE ALARM SETTINGS

1. From the S02 home screen scroll up (+)
or scroll down (-)
highlight 03- PM (Maximum Pressure Alarm).
All manuals and user guides at all-guides.com
to move the cursor to
button to display the
or scroll down (-)
button to
to move the cursor to
Maximum Pressure Alarm Settings
2. The default setting for this parameter is 145.
This number indicates the value used for the
High pressure 'Fault' level. This value remains
active at all times regardless of which 'Table' is
active. It should be set at a level just below the
system pressure relief value(s) and below the
maximum system pressure rating of all air
system components.
3. Press the enter
Maximum Pressure Alarm configuration screen.
The flashing cursor should be displayed
highlighting the Maximum Pressure Alarm
parameter. The values for this parameter are:
The highest value for the Maximum
o
Pressure Alarm setpoint = "The
maximum range of the pressure
transducer used"
The lowest value for the Maximum
o
Pressure Alarm setpoint = "The highest
value from any Table "PH - Pressure
High" Setpoint plus 2 times the "To –
Tolerance"
If PH in Table 1 (T01) is set for 100 PSI,
and PH in Table 2 (T02) is set for 110
and TO is set for 3.0 PSI, then the lowest
Maximum Pressure setpoint would be
116 PSI.
4. Scroll up (+)
until the value is set to a pressure that is just
below your air system requirements. Press the
enter
5. You should be returned to the S02 home screen
and values just entered should appear next to
the PM parameter.
6. After you have completed adjusting the settings
on the S02 screen, press the escape
to return to the page selection screen.
13
button to display the
or scroll down (-)
button to confirm your selection.
button

Publicidad

Tabla de contenido
loading

Tabla de contenido