Sequence Rotation; Operational Functions; Stop; Start - Ingersoll Rand System Automation X4I Manual De Configuración Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 77

SEQUENCE ROTATION

P00
#4
18 / 05 / 2006
Sequence Rotation Display Screen
Day of the week (#4: Thursday), the time of
day (18:00) and the date (18/05/2006) of
the next automated sequence rotation event.
The active 'mode' of operation.
ABCD
The current active rotation sequence
assignment.
Press the escape
button to return to the normal
operational display screen.
NOTE: The sequence assignment can be manually rotated
at any time. When viewing the 'Sequence Rotation'
information screen press the Enter
manual rotation symbols
flash. Press the enter
rotation or the escape
manual rotation.
Automated sequence rotation is not disrupted by a
manual rotation; the next scheduled automated
sequence rotation event will still occur.
All manuals and user guides at all-guides.com
18:00
A B C D
button. The
will appear and
button to execute a manual
button to abandon the

OPERATIONAL FUNCTIONS

STOP

To stop the X4I, press STOP. Dependent on the setup
and configuration of the X4I, the compressors will
function as follows:
If parameter CF=X, then pressure regulation
control is automatically transferred back to each
compressor. The compressor(s) will continue to
operate using the pressure settings programmed
or set in the individual compressor controller(s).
If parameter CF=
compressor in an offload state. If the
compressor is equipped with a main motor run-
on-time function the compressor will run offload
for a period of time and then stop in to a
"standby" or "auto restart" state.
The design of some air compressor control systems may
inhibit automatic transfer of pressure regulation control
to local operation mode. In this instance, the compressor
will not continue production of compressed air. Consult
the air compressor manual or your air compressor
supplier or specialist for details before installing the X4I.

START

To start the X4I press START. If the Prefill function is
enabled, and system pressure is below the set prefill
pressure, the system will enter Prefill mode for the set
Prefill time.
NOTE: The Default setting for Prefill is OFF.
See the section on Prefill in the Operator's Manual
for more information.
To manually skip the Prefill function, press and hold
START for several seconds. When Prefill is complete, if
applicable, the X4I will enter normal operating mode.
The X4I will operate in accordance with the parameters
and options set in the active "Table".
See the section on Tables in the Operator's Manual
for more information.
Each compressor in the system must be started (running
or in a standby or auto restart condition) before X4I
control of the compressor can be established. The X4I
will not start a compressor that is in a stopped condition.
9
, then the X4I will hold each

Publicidad

Tabla de contenido
loading

Tabla de contenido