Compressor Tables Configuration; T01 Tab Screen; High Pressure Set Point Settings; Low Pressure Set Point Settings - Ingersoll Rand System Automation X4I Manual De Configuración Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 77

COMPRESSOR TABLES CONFIGURATION

T01 TAB SCREEN

1. After you have returned to the page selection
screen, scroll up (+)
until the T01 page is highlighted.
T01 Tab Screen
2. Press the enter
selection. The cursor should be flashing on line
01 PH.
T01 Home Page

HIGH PRESSURE SET POINT SETTINGS

1. From the T01 home screen scroll up (+)
or scroll down (-)
highlight 01- PH (High Pressure Set Point).
High Pressure Set Point Setting
2. The default setting for this parameter is 102 PSI.
This setting indicates the High Pressure Setpoint
All manuals and user guides at all-guides.com
or scroll down (-)
button to confirm your
to move the cursor to
that is used to unload the compressor when the
Table is active.
3. Press the enter
Pressure Set Point setup screen. The flashing
cursor should be displayed highlighting 102 PSI.
The values for this parameter are:
The highest value for the High Pressure
o
setpoint = PM "Maximum Pressure
Alarm" minus 2 times TO "Tolerance".
If PM is set for 145 PSI and TO is set for
3.0 PSI, then the highest value for the
High Pressure setpoint would be 139 PSI.
The lowest value for the High Pressure
o
setpoint = PL "Low Pressure" setpoint
plus TO "Tolerance"
If PL is set for 98 PSI and TO is set for
3.0 PSI, then the lowest value for the
High Pressure setpoint would be 101 PSI.
4. Scroll up (+)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
You should be returned to the T01 home screen
and values just entered should appear next to
the PH parameter.

LOW PRESSURE SET POINT SETTINGS

1. From the T01 home screen scroll up (+)
or scroll down (-)
highlight 02- PL (Low Pressure Set Point).
Low Pressure Set Point Setting
2. The default setting for this parameter is 98 PSI.
The 98 PSI indicates the Low Pressure Setpoint
that used to load the compressor when the Table
is active.
3. Press the enter
Pressure Set Point setup screen. The flashing
cursor should be displayed highlighting the 98
PSI. The values for this parameter are:
The highest value for the Low Pressure
o
setpoint = PH "High Pressure" setpoint
minus TO "Tolerance". If PH is set for
17
button to display the High
or scroll down (-)
button to confirm your selection.
to move the cursor to
button to display the Low

Publicidad

Tabla de contenido
loading

Tabla de contenido