en | Product description
224
Minimum
0.25 mm H
0.025 mbar
2.5 Pa
6.3

Detector test

Figure 6.2: FAD-420-HS-EN_SO2_01
1.
2.
3.
4.
5.
6.
7.
7

Technical data

FAD-420-HS-EN
Operating voltage
Maximum current consumption
Permissible air speed
Protection class as per IEC 60529
Safety standards
EMC interference immunity
2015.03 | 6.0 | F.01U.033.733
O (0.01 in. H
O)
2
2
A Fastening screws
B Cover
C Air filter
Switch the FAD-420-HS-EN to test mode on the fire panel.
If you have activated the jumper for the tamper switch, secure a magnet at the reed
switch (E) on the side of the detector housing.
This bridges the tamper switch (F) and allows the cover (B) to be removed without
having to switch off the Smoke Detector (D).
Loosen the fastening screws (A) on the cover and remove the cover (B).
Check both air filters (C) for contamination and replace them if necessary.
If necessary, check and clean the sample tube and ventilation tube.
Test the Smoke Detector (D) with a suitable test aerosol.
Once the detector is checked, reattach the cover, remove the magnets, and set the
detector to operating mode on the fire panel.
Maximum
4.57 cm H
O (1.8 in. H
2
4.48 mbar
448 Pa
D Smoke Detector
E Reed switch
F Tamper switch
24 V DC (15 V DC to 33 V DC)
Approx. 0.51 mA
(Approx. 0.71 mA with FAD-RB-
DIBT Relay Board)
1.5 m/s to 20 m/s.
IP30
IEC 60950 / EN 60950
EN 50130-4
Installation Guide
Duct Smoke Detector
O)
2
Bosch Sicherheitssysteme GmbH