261(PLC: 40262)
T1SetC1
262(PLC: 40263)
T1SetC2
263(PLC: 40264)
T4C1
264(PLC: 40265)
T4C2
265(PLC: 40266)
T1SetH1
266(PLC: 40267)
T1SetH2
267(PLC: 40268)
T4H1
268(PLC: 40269)
T4H2
POWER INPUT
269(PLC: 40270)
LIMITATION
HB: t_T4_FRESH_C
270(P LC: 40271 )
LB: t_T4_FRESH_H
271(PLC: 40272)
T_PUMPI_DELAY
272(PLC: 40273)
EMISSION TYPE
Parameter of the ninth temperature curves for cooling
mode, range: 5~25°C, default setting: 10°C
Parameter of the ninth temperature curves for cooling
mode, range: 5~25°C, default setting: 16°C
Parameter of the ninth temperature curves for cooling
mode, range: (-5) ~46°C, default setting: 35°C
Parameter of the ninth temperature curves for cooling
mode, range: (-5) ~46°C, default setting: 25°C
Parameter of the ninth temperature curves for heating
mode, range: 25~65°C, default setting: 35°C
Parameter of the ninth temperature curves for heating
mode, range: 25~65°C, default setting: 28°C
Parameter of the ninth temperature curves for heating
mode, range: (-25) ~35°C, default setting: -5°C
Parameter of the ninth temperature curves for heating
mode, range: (-25) ~35°C, default setting: 7°C
The type of power input limitation, 0=NON, 1~8=type
1~8, default: 0
Range: 0.5~6 hour, setting interval: 0.5 hour, sending
value=actural value*2
Range: 0.5~6 hour, setting interval: 0.5 hour, sending
value=actural value*2
Range: 0.5~20 hour, setting interval: 0.5 hour,
sending value=actural value*2
Bit12-15: The type of zone 2 end for cooling mode
Bit8-11: The type of zone 1 end for cooling mode
Bit4-7: The type of zone 2 end for heating mode
Bit0-3: The type of zone 1 end for heating mode