Component Overview; Disconnecting The Inverter From Voltage Sources - SMA Sunny Tripower CORE2 Manual De Instrucciones

Ocultar thumbs Ver también para Sunny Tripower CORE2:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 82

4 Component Overview

4
Component Overview
A
Figure 1 : Positions of the inverter components
Position
Designation
A
Left enclosure lid
B
DC SPD assembly
C
AC terminal
D
Cable compartment cover
5

Disconnecting the Inverter from Voltage Sources

Prior to performing any work on the inverter, always disconnect it from all voltage sources as
described in this section. Always adhere to the prescribed sequence.
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1100 V or higher.
Procedure:
1. Disconnect the AC circuit breaker and secure it against reconnection.
12
STPxxx-60-DC-SPD-RM-xx-11
B
WARNING
SMA Solar Technology AG
D
C
L 1
L 2
L 3
P E
Replacement Manual