Dependencies between the "Discrepancy time" and "Input delay" parameters
The configured discrepancy time must be greater than the configured input delay.
Dependencies between the "Startup time of the sensors after short circuit test" and "Time for short circuit test"
parameters
The startup time of the sensor after a short circuit test must amount to at least 1% of the time for the short circuit test.
Switching on the supply voltage L+ for the ET 200SP F-modules and IM
Make sure that the F-module as well as the IM were de-energized at the same time before you switch on the supply voltage
L+ for an F-module. You do not have to observe a switch-on sequence.
Cyclic reading of I&M data
Cyclic reading of I&M data can affect the timing of the F-modules. You should therefore avoid short read cycles of less than
500 ms.
Wire break detection for F-DQ 4x24VDC/2A PM HF fail-safe module up to and including hardware revision level 02
The response threshold of the wire break detection is < 15 mA.
T
acknowledgment time
DAT
F-Module
Digital input module F-DI 8x24VDC HF
Digital output module F-DQ 4x24VDC/2A PM HF
Power module F-PM-E 24VDC/8A PPM ST
Technical specifications
The information on "Permitted potential difference between different circuits" is no longer part of the technical specifications.
Technical specifications, digital output module F-DQ 4x24VDC/2A PM HF (6ES7136-6DB00-0CA0)
Voltage induced on current interruption limited to
Technical specifications, power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)
Voltage induced on current interruption limited to
10
T
acknowledgment time
DAT
23 ms
31 ms
30 ms
-2*47 V, typical
max. -1.5 V
Product Information for the Documentation of ET 200SP Fail-safe Modules