General amendments to the documentation
This Product Information contains amendments and corrections to the documentation of the following ET 200SP fail-safe
modules.
Digital input module F-DI 8x24VDC HF
Digital output module F-DQ 4x24VDC/2A PM HF
Power module F-PM-E 24VDC/8A PPM ST
Digital output module F-RQ 1x24VDC/24..230VAC/5A
The Product Information is part of the product supplied. The statements provided therein should be considered to be more
up-to-date than other documentation if uncertainties arise.
You can use the Power Module F-PM-E 24VDC/8A PPM ST with the standard modules listed under entry ID: 83203124
(https://support.industry.siemens.com/cs/ww/en/view/83203124) within a potential group.
Amendment to chapter 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", 5.1.1.4 "Application:
Wiring of two parallel loads to the digital output, PP switching" and 5.4.2 "Safety-related shutdown of standard output
modules, PP switching" of the manual "Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
WARNING
The light test must be activated if the output channel can permanently carry the "0" signal for 100 hours or more. Consult
the respective requirements of your product standards regarding error detection time.
Addendum to section 5.1 "Applications for the output DQ/P1 and P2" and 5.4 "Applications for the safety-related
shutdown of standard modules" of the manual "Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
WARNING
A defective F-module can result in cyclic "1" signals with the duration of the "Max. readback time switch on test" at the
output DQ/P1 and P2.
Correction of section 3.1 "Terminal assignment" of the manual "Power Module F-PM-E 24VDC/8A PPM ST (6ES7136-
6PA00-0BC0)"
The warning in the section "Redundant ground conductor required" is being omitted, and being replaced by the new warning
in section 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", section 5.1.1.4 "Application: Wiring two
loads in parallel to the digital output, PP switching" and section 5.4.2 "Safety-related shutdown of standard output modules,
PP switching".
Amendment to chapter 5.1.1.2 "Application: Wiring a load to the digital output, PP switching", section 5.1.1.4
"Application: Wiring two loads in parallel to the digital output, PP switching" and section 5.4.2 "Safety-related
shutdown of standard output modules, PP switching" of the manual "Power module F-PM-E 24VDC/8A PPM ST
(6ES7136-6PA00-0BC0)"
WARNING
In this application, you have to connect two ground cables to the BaseUnit for safety reasons. Otherwise, the maximum
residual current at signal "0" (specified in the technical specifications) cannot be maintained if a single ground cable is
interrupted.
Amendment to chapter 5.2 "Application 1: Safety mode SIL3/Cat.3/PLd" of the manual "Digital input module F-DI
8x24VDC HF (6ES7136-6BA00-0CA0)" and section 5.2.2 "Application 1: Safety mode SIL3/Cat.3/PLd" of the manual
"Power module F-PM-E 24VDC/8A PPM ST (6ES7136-6PA00-0BC0)"
Note
SIL3/Cat.3/PLd can be achieved through cross-circuit proof wiring and for the sensor, through application of the principle of
positive opening operation.
Unsupported parameters
The "Pulse stretching" and "Disable dark test for 48 hours" parameters are not supported.
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AJ, 06/2020
9