INSTALLATION
1
Installation requirements:
- All wiring must conform to the National Electrical Code and local codes.
- Cables routed through metal must be protected and insulated by using grommets or bushings.
- The cable for the T5 ZSP Hz motor is replaceable. If it is damaged, replace with the same type of cable. The cable may only be
Installed on the motor by a qualified person. Care must be taken when replacing the cable not to damage the contacts. Continuity
of the earth (ground) connection must be confirmed.
Recommendations: Keep a minimum distance of 8 inches (20 cm) between two T5 ZSP Hz motors. Keep a minimum distance
of 1ft (30cm) between T5 ZSP Hz motors and Hz transmitters. A radio appliance using the same frequency (433,42 MHz) may
deteriorate our product's performance (ex.: hi-fi radio headphones).
Drilling of the tube:
2.17 (55)
0.90 (22.8)
* 310 in lbs (35Nm) max
Assembly:
1
5 in lbs (0.55Nm)
WIRING
2
It is recommended a method of power disconnect for each motor be placed within sight of the motor
to cut power during servicing and facilitate reprogramming.
- Secure the cables to prevent
any contact with moving
parts.
- If the power supply cable is of the
SJTW type and used outside, it
must be protected from exposure
as per NEC.
- The motor must be installed
with a drip loop to prevent water
intrusion.
T5 ZSP Hz
(120V ~ 60Hz)
L1
IP44
L2
ALUMINIUM WHEEL
9910004
5
2
3
10.18
25.18
35.18 • 50.12
Ø3/16
STEHL
Ø1/4
9910004
4
221 in lbs (25Nm) max.
N
L
PE
5136814A
A
ØB
C
Ø min.
22.95
(583)
1.85
3/16
1.02
(47)
(5)
(26)
25.87
(657)
T5 ZSP Hz
MOTOR
CABLE
BLACK
WHITE
GREEN
-20°C / +60°C
Inches (mm)
D
L1
L2
23.46
24.37
(596)
(619)
1.17
(4,2)
26.38
27.28
(670)
(693)
POWER
120VAC
HOT (L)
NEUTRAL (N)
GROUND (PE)
US
1/12